Reductions in maximum flow temperatures in Scottish domestic heating
Research completed: February 2023
DOI: http://dx.doi.org/10.7488/era/3385
Executive summary
Background
Decarbonisation of domestic heating systems is crucial for achieving the Scottish Government’s ambitious climate change targets of net zero emissions by 2045. The transition to zero direct emissions heating systems (e.g., heat pumps, district heating) will require a suite of changes to the Scottish housing stock, including preparing it to operate at lower flow temperatures than the current majority of 70-80°C. Flow temperature is the temperature a wet heating system warms water to before sending it to radiators in different areas of a building.
This study summarises the current evidence for flow temperature reduction in hot water (wet) systems and considers how this might be applied to the Scottish housing stock. Suitability is defined as a dwelling’s ability to reach thermal comfort for a range of external temperature test criteria. We assess the suitability of the present housing stock as it is today and then with two different cost levels of retrofit. The assessment method includes a literature review, stakeholder interviews and scenario modelling to test different temperature cases.
Findings
We have found that most of the Scottish housing stock is currently unsuitable for flow temperature reduction to 55°C or below on a winter peak day (see Figure 1).
Many dwellings in Scotland could reach suitability for 55°C flow temperatures after the inclusion of retrofit(s). Effective retrofit measures include efficiency measures such as wall and/or loft insulation, upgrading radiators or a combination of smaller efficiency measures such as hot water tank insulation, draughtproofing and reduced infiltration measures.
In our higher cost retrofit scenario, 76% of homes become suitable for a flow temperature of 55°C on a winter peak day (see Figure 2). This could prepare the housing stock to be ready for zero direct emissions systems without requiring gas boilers to be removed from homes immediately.
Figure 1 Absolute number of dwellings suitable to meet thermal comfort at each flow temperature (°C) on a winter peak day with no retrofits
Figure 2 Absolute number of dwellings suitable at each flow temperature (°C) on a winter peak day with more extensive, higher cost, retrofits
We find that 30% of the overall housing stock is unsuitable for a flow temperature below 75°C, and 20% require a flow temperature above 75°C. This suggests these dwellings are either running at temperatures higher than 75°C or are currently unable to reach thermal comfort during periods of peak demand.
Fuel bill savings and emissions reduction from reducing flow temperature is significant and range from £151m to £501m in the stringent external temperature test cases. The associated greenhouse gas emission savings are estimated to be 6.17–10.18 MtCO2 equivalent per year, depending on external temperature cases and retrofit scenarios. Exploring the potential for varying flow temperatures throughout the year could be one way to increase savings.
The most important factor when assessing suitability for flow temperature reduction is in setting temperature criteria that captures the needs of occupants. We used particularly stringent criteria in our assessments, requiring a dwelling to be heated to 20°C during the coldest hour of an average or 20-year winter peak. This may not reflect the reality of how heating systems should be, or are currently, expected to perform but it was selected to ensure the heating needs of the most vulnerable households were considered.
Technical Glossary
Flow temperature |
The temperature at which water or another heat transfer medium in a heating system is warmed to before being sent to heating emitters such as radiators in different areas of a building. |
Heating emitter |
A product that sends out heat, used to distribute heat around a building, e.g. radiators. |
Thermal comfort |
The condition of mind that expresses satisfaction with the thermal environment and is assessed by subjective evaluation. |
Building envelope |
The physical separator between the conditioned and unconditioned environment, typically including the building’s floors, walls, windows, and roofing. |
Draughtproofing |
Measures to reduce airflow, such as applying physical fillers and sealants, around doors and windows. |
Reduced infiltration measures |
Measures to reduce airflow throughout the dwelling – this is like draughtproofing measures but is applied to other points of airflow throughout the dwelling. |
Peak (or peak heating hour) |
The calendar hour with the highest measured demand for heating in the previous calendar year, or the timespan being measured if otherwise specified. |
Shoulder season |
The period between typical warming seasons and cooling seasons. This typically refers to spring and autumn when lower demands for heating are observed. The November average is used in this report. |
1-in-20 peak (historic cold snap) |
The peak heating hour as measured over the previous 20 calendar years. This metric is often used to capture “historic” weather events such as cold snaps and heat waves. |
Oversizing factor |
The ratio of peak radiator capacity to peak energy demand in a building. |
U-value |
The U-value, also called thermal transmittance, measures how well a building element conducts heat. It quantifies the heat transfer rate, with lower values indicating better insulation. It is measured in W/(m²·K). |
Specific heat loss |
Specific heat loss refers to the rate of heat loss from a building at a given temperature differential between internal and external conditions. This is measured in W/m2 of building envelope and is dependent on the U-value of the building envelope. |
Introduction
Domestic heating system decarbonisation is crucial for achieving the Scottish Government’s ambitious climate change targets of 75%, 90% and net zero emissions, relative to 1990, by 2030, 2040 and 2045 respectively. The transition to zero direct emissions heating (ZDEH) systems will require changes to the Scottish housing stock. This will potentially including preparing the building stock to operate at the lower flow temperatures that ZDEH options such as heat pumps operate.
Currently, the majority (approximately 85%) of dwellings in Scotland are heated by water based (wet) boiler systems, which typically operate at flow temperatures between 70-80°C. The remaining dwellings are heated by a mix of communal, heat pump, electric and off-grid systems. Flow temperature reduction has the benefit of reducing the energy required to meet the same internal room temperature, thus leading to reduced emissions and fuel bill costs in gas boiler and ZDEH systems alike.
We summarise the current evidence base for reducing flow temperature in the existing housing stock. We consider how flow temperature reduction might be applied to Scottish housing by modelling a range of lower flow temperature and assessing the potential suitability with varying degrees of retrofits.
Findings from literature review and stakeholder interviews
Range of temperatures for consideration
Evidence base for 55°C
According to the Heat Pump Association (see Appendix 8.1), 55°C is considered the “target” temperature for transitioning existing residential heating systems to lower-flow temperature systems. This is because it is an effective and relatively feasible “middle ground” between flow temperatures of current residential gas boiler currently (>70°C) and the direction of travel towards ZDEH technologies such as heat pumps (which operate optimally between 30-55°C).
At 55°C, most condensing boilers will run more efficiently (because more latent heat can be transferred from the flue gases at lower return temperatures) and there will be a reduction of wear and tear caused by cycling at current flow temperatures. Heat pumps, on the other hand, will reach the limits of their peak efficiency at approximately 55°C; at higher flow temperatures, efficiency will drop below quoted performance.
We found wide agreement in the stakeholder interviews (see Appendix 8.1 for stakeholder engagement overview) that most homes in the UK, and most homes in Scotland, will be able to run heating systems at 55°C without significant retrofitting. According to the CCC (2022), based on a report conducted by Nesta and Cambridge Architectural Research (2022), approximately 27% of homes in the UK currently are suitable for flow temperature reduction based on assumed ancillary attributes (namely radiator and pipework suitability). It is our understanding that a property assessment was not undertaken as part of the Nesta/Cambridge work. This estimate is about half of that found in previous research (Element Energy, 2021), which found that 53% of the UK stock was able to run at 55°C on a typical winter day (the percentage is reduced to 10% to reach thermal comfort on a winter peak day).
It was the opinion of our interviewed stakeholders that most homes in Scotland can successfully be run at 55°C, and that there were few attributes that would rule out this flow temperature (see Appendix 8.4).
Potential for further reduction
It is difficult to transition the housing stock to even lower flow temperatures below 55°C. The proportion of homes which are suitable without any works (or without major works) is significantly lower. Stakeholders suggested that some homes may not be suitable at all, but it is unclear if there was any tangible evidence or guidelines this was based on.
Our previous work (Element Energy, 2021) showed that the percentage of stock suitable for reduced flow temperatures reduces from 53% to 25% at 50°C, 6% at 45°C and <1% at 40°C. On a winter peak day (with an assumed external temperature almost 10°C lower) these proportions of houses suitable reduce to 3% at 50°C, 1% at 45°C and <1% at 40°C.
At lower flow temperatures, the specific heat loss of a property becomes increasingly important. Specific heat loss, in practice, is an indicator of how much heat will be required to maintain thermal comfort. Heat loss tends to have an inverse relationship with efficiency – a home with a low specific heat loss rate will be highly efficient, while homes with a high heat loss rate tend to be less efficient.
This is an important consideration when assessing the suitability of reducing flow temperature because in a home without retrofitting, a reduced flow temperature will decrease the amount of heat delivered to a room. If a room is difficult to heat because the home has a high heat loss rate, it becomes increasingly difficult to reach the desired temperature of that room because the system cannot adequately deliver or retain heat.
In this situation, one or both of the following paths can be taken to make a home suitable for a lower flow temperature:
Increase delivered heat. To do this, specific components of the heat system may need to be replaced or adjusted. The two key components are pipework, which impacts the flow rate of water through the system; and radiators, which emit heat transferred from the water. Existing pipework may need to be replaced to allow for a higher flow rate (which would help move more heat through the radiator in a given time period). Radiators could be replaced with larger units, which will allow more heat to be emitted due to an increase in absolute surface area. One or both options will increase delivered heat.
Decrease specific heat loss. To do this, a home needs to become more efficient through retrofitting to increase efficiency and airtightness. The two most important retrofits that can be undertaken are insulation (loft or wall) and window glazing. In addition, draughtproofing can be applied to windows and doors. These measures will lead to a higher rate of heat retention, meaning the absolute amount of heat that needs to be transferred to reach thermal comfort in a home is decreased.
Building envelope measures to increase suitability for flow temperature reduction
Increasing the efficiency of the building envelope decreases specific heat loss, thus supporting flow temperature reduction. Stakeholder interviews emphasised the importance of home retrofitting and maintenance, especially where homes are poorly insulated, as it also leads to heat demand reduction.
Home insulation
In general, more insulated homes will be more suitable for lower flow temperatures, due to the lower heat demand to reach thermal comfort. It is unlikely that there is a situation in which a home is “too insulated”, except if this insulation does not allow for moisture to be driven from the masonry.
Interviewed stakeholders considered insulation as one of the most influential aspects for suitability to operate at lower flow temperatures. Despite a general concern that traditionally built homes were unlikely to be suitable for a lower flow temperature, one stakeholder suggested loft and wall insulation is likely to be sufficient. It makes little difference if the loft is used as a room (CCC, 2022), as insulating in either case will decrease the home’s heat loss, but additional care should be taken due to the likely increased cost.
Window glazing
Similar to insulation, improving window glazing to double glazing or secondary glazing, is always beneficial for increasing the suitability of homes for reduced flow temperatures because they reduce the specific heat loss of a property. While triple glazing may offer benefits, it can introduce ventilation concerns and results in a lower marginal efficiency gain for flow rates compared to the adoption of double glazing.
Both double glazing and secondary glazing can effectively lower heat loss, but double glazing is a more expensive process and involves replacing entire units. Replacing existing windows with double glazed windows may be more difficult or restricted in traditional homes due to conservation/listed building status or for aesthetic reasons. Care should also be taken to balance ventilation requirements with increased glazing.
Ancillary components for the reduction of flow temperature
Ancillary components are key to effectively increasing delivered heat and/or decreasing specific heat loss. The overall efficiency of the heating system and, more generally, home energy efficiency will increase the suitability for flow temperature reduction. Some ancillary components are particularly important to a home’s suitability, and these are discussed in the following sections.
Radiators
When radiators are fitted, the size of radiator suitable for a home is determined with consideration to the flow temperature the heating system runs at, alongside flow rate, to determine an adequate size to meet thermal comfort. If all else remains constant but the flow temperature is reduced, it is possible that the heat transferred to the radiator will not be sufficient. To mitigate this, existing radiators can be replaced with larger units which can transfer more heat, but this may be more expensive than other retrofit measures.
Pipework
Pipework is likely to be a key attribute for suitability of a home to increase the flow rate of the heating system. Like radiators, piping tends to be sized for the heating distribution system. Pipework may need to be replaced to account for a lower flow temperature, but our previous work (Element Energy, 2021) and stakeholders consulted had mixed opinions as to whether increased flow rate was an effective counterbalance to reduced flow temperature, and whether it would be required.
During our engagement with Renewable Heat (see Appendix 8.1, it was suggested homes were built or had heating system replacements between the 1980s and 2002 are more likely to require pipework replacements. During this period, a copper shortage led to smaller piping instalments across the industry. Due to an update to buildings regulations in 2002 this is not an issue for newer builds.
Pipework, compared to other ancillary components, is particularly susceptible to maintenance problems leading to inefficiencies. For example, past analysis (Element Energy, 2021) found that efficiency reductions due to sludge (15%), hydraulic imbalance (10%), air (6%) and limescale (15%) can impact the ability for a heating system to reach thermal comfort.
Other considerations
The efficiency improvements possible for pipework highlight the importance of regular maintenance for heating systems. Heat distribution systems should have annual maintenance servicing, but our recent analysis (Element Energy, 2021) found that currently only 20% currently participate in this. Proper maintenance would increase overall system efficiency, thus making reaching thermal comfort at lower flow temperatures more feasible.
Key risks to reducing flow temperature
Thermal comfort (human and fabric)
Reaching adequate thermal comfort is the goal of assessing the feasibility of lowered flow temperatures. There are clear guidelines (British Gas, 2022) set by knowledgeable bodies (including the Lullaby Trust, Energy Savings Trust, World Health Organisation and Age UK) for temperatures homes should be heated to depending on the occupant, including:
- Homes with new-borns should be heated between 16–20°C
- Homes with healthy occupants should be heated to 18°C
- Homes with occupants which are old, young or unwell should be heated to 20–21°C (some recommendations state homes can be warmed to 18°C as long as the main living space of the older occupant is heated to 21°C)
In practice, there are many instances where these temperature thresholds are not met, for technical and behavioural reasons. This complicates suitability assessments, because setting the above thresholds may require heating systems to perform to temperatures that are not used in practice. Some behavioural reasons homes are not heated to the above thresholds may include:
- Turning heating on/off in bursts, instead of maintaining a constant temperature
- Regularly keeping heating at a comfortable temperature below the guideline temperature (for example, 18°C instead of 21°C)
- Refraining from heating despite discomfort (often associated with fuel poverty)
The disconnect between recommended thermal comfort and behavioural practice makes assigning a temperature threshold for lowered flow temperature complex, but previous reports and stakeholders generally agree a reasonably lower flow temperature will not cost consumers’ thermal comfort. It should be noted that special care may need to be taken for identified vulnerable consumers.
Nesta and The University of Salford (2022) suggests lower flow temperatures may lead to longer warming times, if flow rate and radiator size are not changed at the same time, due to the decrease in transferable heat. The acceptability of increased warming times would likely require a behavioural study.
Reduced flow temperature could also mean that room temperature cannot reach thermal comfort guidelines. It is not clear by how much and if this would cause a reduction from current practice. In the Nesta and The University of Salford (2022) study, homes with boilers and reduced flow temperature were able to reach within 0.5–2°C of thermal comfort (set at 21 °C in the living room, 22°C in the bathroom and 18°C in all other zones) on an average heating day, which is likely to be sufficient for most homes with healthy consumers.
Similarly, reduced flow temperature may make reaching thermal comfort on peak heating days more difficult. Further testing is likely to be required to better understand the impact of heating during periods of lower external temperatures. It could be the case that systems with reduced flow temperatures are within 2°C of thermal comfort on these peak days, which may be acceptable to occupants, but this is masked by the binary threshold of reaching thermal comfort.
Stakeholders agreed that buildings generally do not suffer from damp, moisture, and mould when the home is heated to human thermal comfort levels. Ensuring thermal comfort for humans is likely to provide adequate heating and avoid impacts on the building structure as well.
Unsuitable ancillary components
In many homes, reducing flow temperature without also retrofitting (e.g., adding insulation, replacing pipework, upgrading radiators) may cause the system to under-perform. The home would not reach thermal comfort due to the reduction of transferable heat and unimproved specific heat loss or system efficiency. Conversely, if the heating system is replaced before the home is retrofitted (insulation and window glazing, for example) the heating emitter could be oversized, causing increased cycling or inefficiency. To ensure this is not the case, retrofitting measures should be implemented before or in tandem with reducing flow temperature for an individual property.
Concerning the building masonry, the level of energy efficiency retrofitting should be balanced against the need to ventilate the home properly and drive moisture out of the walls to avoid deterioration of the home’s exterior. This is a particular concern in older dwellings but should be considered for all dwellings. One stakeholder suggested approximately 100mm of wall insulation would be a good balance, but previous analysis suggests this may not be adequate insulation for energy efficiency. More research may be needed to understand this balance better.
Costs incurred by significantly lower temperatures
The Heat Pump Association suggests homes which are not properly retrofitted to increase heat delivery or decrease specific heat loss could be required to heat their homes for significantly longer periods of time, and thus higher overall energy consumption. This, in turn, would lead to an increase in both energy usage and the absolute value of energy bills.
Our engagement with the Heat Pump Association suggested that lower temperatures will require increasingly airtight, well-insulated homes with larger radiators to ensure the heat loss doesn’t rise above 150W/m2. For most homes, a flow temperature reduction to 45°C should not incur significant financial costs. To reduce flow temperatures further, homes must be increasingly efficient and airtight, potentially with larger radiators. These costs are likely to be prohibitive for many without financial support.
Key benefits to reducing flow temperature
Energy savings
When combined with required retrofits, reducing flow temperatures is expected to reduce energy use significantly. Previous work suggests savings are roughly correlated to the degree of change between the baseline temperature and new flow temperature. There are continued savings to be achieved by lowering flow temperature below 55°C.
Nesta and the University of Salford (2022) found 16–23% energy savings in gas used for heating when flow temperatures as low as 48.2°C were tested. This correlates to roughly 12–17% of overall gas savings at household level (assuming heating accounts for 75% of gas use in residential buildings). At low flow temperatures, care must be taken to ensure a boiler’s intended operating regime is maintained, for example maintaining efficiency of a condensing boiler.
These energy savings will lead to savings in in fuel bill costs at the household level, due to the lowered energy required to heat the distribution system. The level of fuel bill savings will depend on a combination of flow temperature and fuel prices.
Emissions savings will also be a result of flow temperature reduction. Most homes in Scotland are heated with natural gas, so the direct reduction in natural gas use will reduce emissions. For homes heated with electricity, reducing electricity use on a grid that is not completely zero carbon will have indirect emissions reductions.
ZDEH readiness
The Salford Energy House (2022) study shows that even homes using boilers can benefit from reduced flow temperatures. The retrofits and system upgrades required for such a switch are often “no regret” decisions, no matter what future heat source the home will use (whether it be natural gas, hydrogen, electricity or district heating) because these changes improve the overall efficiency of the homes.
In general, low carbon heating systems run on lower temperatures, so all ancillary works, maintenance and upgrades will smooth the transition to a low carbon heating system across all home archetypes. There was agreement amongst stakeholders that ancillary works and reducing flow temperatures prepare houses for ZDEH systems. Systems with lower flow temperatures (including those currently using gas) use less overall energy to meet demand because the whole home system is more efficient.
Methodology for assessing flow temperature reduction
Overview
This study seeks to model the suitability for potential flow temperature reduction in heating systems in Scottish homes. The ideal methodology for an assessment of flow temperature reduction potential would include a property-specific heat loss calculation. In lieu of this, our method uses heat demand and property characteristics as a proxy for current ability to meet demand.
Property characteristics including levels of insulation, current heat distribution systems and heat demand was provided by the Home Analytics Scotland (HAS, 2022) dataset. The HAS dataset provides characteristics of the Scottish housing stock based on a compilation of datasets and modelling. This dataset is the result of whole-stock modelling conducted by the Energy Saving Trust. It should be noted that there is a discrepancy between the number of properties modelled as part of the work in this report (2,747,067 dwellings) and data in the Scottish House Condition Survey (Scottish Government, 2021) which accounts for approximately 10% less homes. We believe this is due to the modelling method used by Home Analytics Scotland.
Our assessment of suitability was led by stakeholder interviews and previous work (Element Energy 2020b, 2021). The previous work developed a suitability assessment for the UK housing stock based on dwellings’ current oversizing factor.
Retrofit options were modelled using prices for materials and labour for individual retrofits taken from previous work for the CCC (Element Energy, 2020a).
Results from suitability modelling were then translated into energy demand reduction using heat demand profiles from the National Energy Efficiency Data-Framework (NEED), Scottish weather data and heat system efficiencies. Cost and emissions savings were calculated using up-to-date fuel prices and emissions data from recent Element Energy analysis.
Modelling approach
Defining suitability
The first step in this study’s methodology was defining suitability, which considered both internal temperature and external temperature. Both sets of temperatures were based on previous work commissioned by BEIS (Element Energy, 2021).
The target internal temperature was 20°C, which is the lower end of the World Health Organisation’s (WHO) recommended internal temperature range for dwellings with vulnerable occupants. While not every home has vulnerable occupants, there is no robust way to predict what homes will be occupied by vulnerable consumers, and as such an internal temperature target was chosen which could meet the needs of any consumer at any hour of a given year. This temperature is also aligned with the Microgeneration Installation Standard (MIS) 3005 (MCS, 2019), which recommends living zones maintain a temperature of 18–22°C.
We tested a dwelling’s ability to reach thermal comfort (20°C) at various external temperature cases:
- Winter peak, our central case which tests suitability during the peak heating hour of an average year.
- 20-year peak, which tested a dwelling’s ability to reach thermal comfort during the peak heating hour of a historic cold snap. Also referred to as a historic cold snap.
- Winter average, which tested a dwelling’s ability to reach thermal comfort during an average heating hour in an average winter (as opposed to the peak heating hour in the winter peak).
- November average, which tested a dwelling’s ability to reach thermal comfort during an average heating hour in an average “shoulder season” (the heating hour used in this study is taken from an average November).
Suitability at a set internal and external temperature test case was measured based on the dwelling’s oversizing factor, which is the ratio of peak radiator capacity to peak demand. See Appendix 8.2 for more information on why oversizing factors were used in lieu of specific external temperatures. Based on this oversizing factor, we know what minimum flow temperature each dwelling can operate at and still meet thermal demand. Oversizing factor ranges are set out in the BEIS study (Element Energy, 2021). Oversizing factors of between 1.00 and 1.20 suggest a dwelling’s radiator capacity is adequately sized for the dwelling, while an oversizing factor under 1.00 suggests a heat distribution system will not be able to reach thermal comfort and a factor of over 1.20 suggests a heat distribution system is larger than required for the dwelling at a given flow temperature.
Archetyping and radiator mapping
The housing stock was aggregated into seven archetypes with the aim of modelling the suitability and impact of flow temperature reduction for a set of “average” homes. These archetypes were primarily based on stakeholder insights on the key determinates of flow temperature reduction based on their experience (age and house type). These were compared to the archetype design of the BEIS study, which used similar archetypes. The seven archetypes were:
- Pre – 1919 flats (approximately 10% of stock)
- Pre – 1919 houses (approximately 7%)
- 1919 – 2002 flats (approximately 23%)
- 1919 – 1949 houses (approximately 6%)
- 1950 – 1983 houses (approximately 27%)
- 1984 – 2002 houses (approximately 10%)
- Post – 2002 dwellings (flats and houses) (approximately 14%)
All dwellings in the HAS database were assigned an archetype, which was used for energy demand reduction, fuel bill and emissions savings calculations. We then assigned oversizing factors. Extrapolation of BEIS (Element Energy, 2021) survey data to the entire UK housing stock provided a distribution pattern across archetypes. This was used to assign oversizing factors for Scottish dwellings across the archetypes. Dwellings surveyed in the BEIS study were assigned archetypes from the above list and reassigned a proportion of the archetype stock that they represented based on extrapolation from the original study which maintained the robustness of the original study’s housing stock mapping.
The clearest relationship observed in this data was that between building footprint and radiator capacity, with larger dwellings tending to have larger capacities. Dwellings in the BEIS survey and HAS dataset were ordered by archetype and building footprint. The radiator size, building peak demand and oversizing factors were assigned to dwellings from smallest to largest building footprint, maintaining the correct proportions in the housing stock. For example, if the smallest surveyed home in the pre-1919 flats archetype was found to represent 2.7% of the stock, this dwelling’s data was assigned to the smallest 2.7% of HAS dwellings in the same archetype, and so on. This allowed the data to maintain the same oversizing factor distribution.
Suitability modelling
The suitability of the current housing stock portfolio was modelled based on the minimum flow temperatures each HAS dwelling could operate at using the oversizing factor. Retrofit packages were assigned to dwellings based on their archetype and existing levels of insulation. Two retrofit scenarios were modelled:
- The Lower cost retrofit scenario, where retrofit package costs could total approximately £2000 per dwelling, and
- The Higher cost retrofit scenario, where retrofit package costs could total up to 10% of the cost of a whole-home renovation. To determine this cost, the average price of a whole home renovation was taken for an “average” home, which was then scaled up or down for each archetype. This led to a range of costs between £6,000 – £12,000 (see Table 1 for these costs).
Flats |
Mid Terrace |
End Terrace |
Semi Detached |
Detached |
Bungalow | |
Maximum cost (£/dwelling) |
6,123 |
7,459 |
9,106 |
10,670 |
13,585 |
11,143 |
Table 1 Retrofit costs for dwellings in the Higher cost retrofit scenario, by dwelling type
Dwellings were assigned retrofit packages based on the specific dwelling attributes in the HAS dataset. Because these attributes are in the original dataset, retrofit packages were assigned regardless of what external temperature case or radiator sensitivity was being tested.
Each dwelling was assigned two packages, one for each retrofit scenario (see Appendix 8.3 for list of retrofits). In both scenarios, most homes are assigned standard energy efficiency measures and/or radiator upgrades (75% and 71% in the Lower and Higher cost retrofit scenarios, respectively, see Figure 3 below). For many dwellings, additional insulation measures are required based on current level of insulation modelled by HAS. In some of these cases, dwellings can be insulated within the approximately £2000 price bracket, while other homes are more expensive to insulate. In these situations, the cost to insulate falls within the more expensive retrofit scenario.
Retrofit packages took a fabric first approach, prioritising measures with higher efficiency gains (mostly wall and loft insulation), then measures with lower-efficiency gains (increased draughtproofing, reduced infiltration measures and hot water tank insulation) and finally radiator upgrades where applicable. See Appendix 8.3 for details.
After a retrofit package was assigned to all dwellings in each retrofit scenario, the efficiency increases are applied to the dwellings assigned oversizing factors. This study assumed a direct relationship between energy efficiency increases and demand reduction, so an efficiency increase of 18% was applied by reducing the oversizing factors by 18%. These new oversizing factors were used to reassign dwellings to minimum flow temperatures. In practice, this may not reflect how efficiency increases are observed in dwellings, but an implementation-based study would be required to accurately capture this.
Fuel bill and emissions modelling
Results were aggregated at archetype level and used to find archetype-level energy demand reduction for fuel bill and emissions savings modelling. To calculate energy demand reduction at the archetype level, the average energy demand was calculated from the NEED (BEIS, 2022). Hourly energy demand profiles were calculated using the Watson method (Watson et al., 2019). We assumed all dwellings currently operate at 75°C flow temperature. The difference between 75°C flow temperature and lower temperatures (down to 50°C) was calculated based on the proportion of the stock which could support this for different external temperature case and retrofit scenarios. All dwellings suitable at temperatures below 50°C were modelled using 50°C savings, due to uncertainty over some boiler’s efficiency at lower temperatures. The cost and emissions modelling outputs were expected to be conservative estimates for fuel bill and emissions savings, due to not capturing the potential savings from 85°C to 75°C and temperatures under 50°C.
To calculate fuel bill savings, two fuel prices (representing a historic average and more recent fuel costs) were used to give a range of savings based on the energy demand reduction on national, archetype and archetypal individual dwelling levels.
To calculate emissions savings, the average natural gas emissions in Scotland were applied to the energy demand reduction on national, archetype and archetypal individual dwelling levels. In this calculation, all dwellings were modelled as gas boilers due to the overwhelming majority of boilers in the breakdown of heat distribution systems in the Scottish housing stock. Only 15% of homes do not currently use gas boiler systems, instead running on electricity or off-grid heating systems. Due to higher price per kWh for electricity, we expect these modelled results to be conservative estimates.
Method limitations
This study sets out to model flow temperature reduction suitability, for which practical research has not been conducted previously on Scottish housing stock. Our study aggregated several data sources and relied on previous research to assess suitability in lieu of property-by-property heat loss calculations and real time case studies for retrofitting and monitoring. As such, the method has several limitations that should be acknowledged when considering findings and conclusions (see Table 2 below for an overview of these limitations).
Limit |
Rationale |
Impact |
---|---|---|
Mapping radiator capacity, heat demand from BEIS (Element Energy 2021) study |
UK/Scottish subset were reasonably aligned; allowed bigger spread of radiator capacity |
This means a key element of the suitability criteria is modelled based on UK stock when ideally, we would have data from Scottish property surveys. In addition, this may predispose certain archetypes to being unfairly penalised or rewarded in the suitability modelling based on the smaller sample of dwellings surveyed as part of the BEIS study. This may be the case for the pre-1919 houses, for example, which are difficult to make suitable. |
Lack of available data on ancillaries such as pipework |
Data not available, so modelling would not have been robust |
This factor for flow temperature reduction could not be assessed at present. Stakeholders provided useful insights and guides for further study. We confirmed that pipework was not an essential upgrade to meet the suitability levels we modelled but could be an additional factor to further increase proportions of stock that are suitable. |
Thermal comfort was set at 20°C for all scenarios |
We felt it was important to keep conservative estimates for internal temperature (led by WHO health standards for vulnerable occupants) |
The use of a relatively high internal temperature target risks unfairly comparing dwellings with lower flow temperatures to a counterfactual that does not exist (because homes are often not heated to 20°C, and many homes are currently unsuitable for this level of heating). |
Assume all current flows are 75°C in cost and emissions modelling |
No reliable data to allow us to assign a proportion of the stock to higher flow temperatures |
This may give a conservative estimate to fuel bill and emissions savings (because it captures the change from 75°C to X°C, so the additional savings from 85°C to 75°C are not accounted for). |
All costs are set at 2022 prices (adjusted from 2019 data) |
Lack of more up to date data with the same level of robustness |
Does not consider inflation in future years (a retrofit package in 2024 may be pushed into a higher cost bracket by inflation or other market pressures in future years). |
Table 2 Summary of method limitations and key assumptions with rationale and impact
Modelling results
Overview
We find that the majority of Scottish housing stock is currently unsuitable for flow temperature reduction to 55°C or below on a winter peak heating hour. However, more than half (60%) of the stock is suitable for a flow temperature reduction during the less stringent test case using the winter average. Both retrofit scenarios considered increase suitability for flow temperature reduction across all external temperature cases and home types. With Higher cost retrofits, between 64% (winter peak) and 97% (November average) of homes become suitable for a flow temperature of 55°C or below.
Suitability now (2022) |
Suitability with lower cost retrofits |
Suitability with higher cost retrofits | |
Winter peak |
15% |
55% |
76% |
20-year peak |
7% |
41% |
64% |
Winter average |
60% |
85% |
94% |
November average |
80% |
92% |
97% |
Table 3 Suitability for Scottish housing stock for flow temperatures of 55°C for different temperature cases
Winter peak
The winter peak temperature case measures a heat system’s ability to maintain thermal comfort during the peak heating hour in an average year.
Before Retrofit
Without retrofits, 15% of the housing stock (approximately 410,000 dwellings) in Scotland are suitable for flow temperature reduction to 55°C (See Figure 4 and Figure 5). Most of these dwellings are flats and post-2002 properties. 30% of post-1919 flats are suitable for flow temperature reduction, and 27% of post-2002 flats and houses. Combined, these two archetypes represent 75% of the suitable stock, and 11% of the overall stock. These two archetypes also capture the portions of the stock that can reduce to the lowest flow temperature without retrofits. In both archetypes, a small subset of homes is suggested to be suitable at a 40°C flow temperature without retrofits (7% of suitable post-1919 flats and 1% of suitable post-2002 flats and houses).
Figure 4 Proportion of stock suitable for 55°C, by archetype (no retrofit scenario)
Figure 5 Dwellings suitable for each flow temperature (cumulative, no retrofit scenario)
Pre-1919 houses and flats and mid/late-century houses (1919-2002) are least suitable for 55°C flow temperatures, all having less than 10% of the archetype stock suitable. The majority for each archetype would be able to reduce flow temperature below 75°C (Figure 5). For example, among pre-1919 flats, 58% of homes are suitable for flow temperatures between 60°C and 70°C.
Pre-1919 houses are not suitable for flow temperatures of 55°C. This result is directly related to the archetype’s lower proportion of adequately sized radiators from the mapping exercise and may also be related to the high heat loss rates in these dwellings. This archetype will require more significant energy demand reductions for homes to reach lower flow temperatures. Despite this, there is a proportion of the stock suitable for a more modest flow temperature reduction, with 30% of the stock being suitable to reduce to flow temperatures between 60°C and 70°C.
30% of Scottish housing stock is currently unsuitable for flow temperature below 75°C. 20% of the stock may also be unsuitable to run at 75°C. This suggests these dwellings are either running at temperatures higher than 75°C or are currently unable to reach thermal comfort during periods of peak demand.
Lower cost retrofit scenario
Figure 6 Proportion of stock suitable for 55°C, by archetype (Lower cost retrofit scenario)
Lower cost retrofit packages are effective in increasing the proportion of homes suitable at a range of lower flow temperatures. After retrofits of around £2k, the proportion of homes suitable for 55°C increases to 55%. In addition to homes being suitable for 55°C, 36% of homes are suitable for lower flow temperatures.
Figure 7 Dwellings suitable for each flow temperature (cumulative, Lower cost retrofit scenario)
Post-1919 flats and post-2002 archetypes continue to be most suitable, while the pre-1919 flats and houses and mid/late century (1919-2002) house archetypes had lower suitability, see Figure 6 and Figure 7. While the archetypes maintained the same relative standing, there are large differences in terms of proportions of the archetype stock that become suitable at lower flow temperatures.
The biggest beneficiaries of lower cost retrofits are the 1919-2002 house archetypes and the pre-1919 flat archetype. The absolute value of suitable homes increased between factors of 5x and 11x (pre-1919 flats and 1919-1949 houses, respectively).
Before retrofits are applied, older dwellings are generally less suitable for lower flow temperatures (see Figure 4). When retrofits are applied, the age of a dwelling appears to matter less than dwelling type (flat or house) with the suitability of pre-1919 flats being similar to houses built from 1950-2002.
The large proportion of the stock that becomes suitable after lower cost retrofits suggests that many dwellings in Scotland may be close (in monetary terms) to suitability for flow temperatures of 55°C. If 55°C is chosen as a “target” temperature, this suggests many homes in Scotland could achieve this target, even with stringent suitability criteria, for a relatively small amount of money. One or two larger efficiency measures (wall and/or loft insulation), an ancillary upgrade (radiators) or three smaller efficiency measures (hot water tank insulation, draughtproofing and reduced infiltration measures) would be required.
Higher cost retrofit scenario
After more extensive retrofits, 76% of the housing stock reaches suitability for reduced flow temperatures of 55°C. Similar, to the base and lower cost retrofit scenario, the post-1919 flats and post-2002 dwellings have the highest rates of suitability (see Figure 8). All archetypes other than pre-1919 houses are above 66% suitability for 55°C flow temperatures within their respective archetype stocks. The archetype with the largest change between scenarios is the pre-1919 homes, with suitability increased by a factor of over seven. In this scenario, almost half of the stock in this archetype reaches suitability (46%).
More homes in this scenario can reach even lower flow temperatures (i.e., flow temperatures between 30°C and 50°C). However, the lower cost retrofits changed the proportion of suitability for 55°C for a higher absolute number of homes than the higher cost retrofits (an additional ~1 million homes suitable, compared to an additional ~600,000 homes).
Figure 8 Proportion of stock suitable for 55°C, by archetype (Higher cost retrofit scenario)
Figure 9 Dwellings suitable for each flow temperature (cumulative, Higher cost retrofit scenario)
20-year peak (historic cold snap)
The 20-year peak temperature case is our most stringent external temperature case, testing the ability for a dwelling to meet thermal comfort in a historic cold snap (the coldest day recorded in a given postcode for the past 20 years).
Without retrofits, the proportion of homes suitable to reduce to a flow temperature of 55°C include is only 7% of the stock (see Figure 10 and Figure 11), mostly consisting of post-1919 flats (4%) and post-2002 houses and flats (2%).
Some housing remains suitable for a flow temperature reduction below 75°C. Most suitable homes are post-1919 flats (15%), 1950-1983 houses (11%) and post-2002 flats and houses (10%).
In this case, over half (52%) of dwellings cannot meet thermal comfort below 75°C. In addition, 33% of the stock is not suitable for 75°C and is either currently operating at a higher flow temperature or would be unable to meet thermal comfort during a 20-year peak/historic cold snap.
Figure 10 Proportion of stock suitable for 55°C, by archetype (no retrofit scenario)
Figure 11 Dwellings suitable for each flow temperature (cumulative, no retrofit scenario)
Lower cost retrofit scenario
The application of lower cost (~£2k) retrofits also brings a significant portion of the housing stock to suitability for 55°C flow temperatures. 40% of the total housing stock could reach suitability even during a 20-year peak/historic cold snap (see Figure 12 and Figure 13).
Post-1919 flat and post-2002 dwellings archetypes continue as most suitable archetypes, both increasing by just over a factor of four. Combined, the suitable stock in these two archetypes represents almost one quarter of the total housing stock (23%).
Figure 12 Proportion of stock suitable for 55°C, by archetype (Lower cost retrofit scenario)
Figure 13 Dwellings suitable for each flow temperature (cumulative, Higher cost retrofit scenario)
Before retrofits, a correlation between age and suitability could be observed, with newer homes having slightly higher rates of suitability. After retrofits, the 1919-1949 homes and 1984-2002 houses have similar rates of suitability (24% and 27% respectively), while 10% more houses in the 1950-1983 archetype are suitable (36%). This suggests more houses in this archetype had oversizing factors on the higher end of each range, thus the same retrofit measure could have transitioned one home to 55°C and a house from one of the other archetypes to only 60°C. It could also suggest that more houses in this archetype required wall or loft insulation, and thus benefited more than other archetypes which received smaller energy efficiency uplifts from the “standard” measures.
Higher cost retrofit scenario
The archetypes with the highest proportions of suitability continue to be the post-1919 flats and post-2002 dwellings (78% and 92% of their respective stocks, and 32% of the total stock, see Figure 14 and Figure 15). All archetypes other than pre-1919 houses improve suitability for 55°C flow temperatures to above 51% of their respective archetype stock. In total, 64% of the stock becomes suitable after more extensive retrofits.
The change in suitability across the archetypes between the lower and higher cost retrofits are larger than in the winter peak case. Therefore, if the 20-year peak was chosen as the external temperature case to assess dwelling suitability, higher cost retrofits would be required achieve a high degree of suitability for lower flow temperatures. The absolute number of stock suitable would still be lower than in the other external temperature cases considered.
Figure 14 Proportion of stock suitable at 55°C, by archetype (Higher cost retrofit scenario)
Figure 15 Dwellings suitable for each flow temperature (cumulative, Higher cost retrofit scenario)
Average external temperature cases
The two ‘average temperature’ cases (winter average and November average) were tested to gauge the suitability of dwellings under less stringent criteria. The results show that with less stringent criteria, much larger proportions of the stock are already, or can be made suitable, for 55°C and lower flow temperatures. See Appendix 8.5 for full archetype results.
The results show that 60-80% of homes are already suitable for 55°C flow temperatures for these less stringent external temperature cases. Lower cost retrofits increase this to 85-92% (for winter average and November average respectively). Higher cost retrofits result in almost all homes being suitable for 55°C (94-97%).
Importance of radiator upgrades
In half of the model runs, we investigated a reduced potential for radiator upgrades in all dwellings. The intention was to model the potential for flow temperature reduction when there were significant barriers to radiator upgrades (which could be caused by impracticalities or aesthetics).
In the winter peak cases, reducing radiator uptake decreases the suitability of the stock at every flow temperature tested. This demonstrates that upgrading radiators could be a key retrofit measure for facilitating flow temperature reduction.
Figure 16 Comparison of dwellings suitable at each flow temperature (cumulative) when reduced and recommended rates of radiator uptake are tested in peak external temperature cases, Lower cost retrofit scenario (above) and Higher cost retrofit scenario (below)
Fuel bill and emissions modelling
The final step in this study is translating energy demand reductions from lower flow temperatures into fuel bill and emissions savings estimates by archetype.
Fuel bill modelling
At a flow temperature of 55°C, dwellings can save between £50 and £300 per year depending on the archetype and fuel cost scenario. The ranges for each archetype are set by applying low and high fuel costs to the archetype’s average annual heat demand from the NEED database (BEIS, 2022). As such, this is reflective of the archetype’s average energy demand patterns as opposed to being reflective of anything tested or modelled in the suitability assessment detailed above. Based on the NEED data, the flat archetypes and 1984-2002 houses will potentially save the most in fuel bills on a per dwelling basis (see Figure 17).
Figure 17 Cost savings when moving from 75°C to 55°C (showing cost range from 4.5p/kWh and 10.3p/kWh)
When aggregated, the potential for fuel bill savings is significant (Table 4). At the lower fuel price, savings range from £151m-£249m depending on the temperature case and retrofit scenario. Higher fuel prices increase this to £345m-£624m.
Lower cost retrofits |
Higher cost retrofits | |||
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price | |
Winter peak |
£181m |
£414m |
£219m |
£501m |
20-year peak |
£151m |
£345m |
£198m |
£454m |
Winter average |
£233m |
£580m |
£244m |
£624m |
November average |
£244m |
£558m |
£249m |
£570m |
Table 4 Aggregated total fuel bill savings per year for all temperature cases and retrofit scenarios (at both fuel prices)
Table 5 shows the potential savings if all dwellings’ flow temperatures are reduced as low as they are suitable higher cost retrofits are applied at archetype level. In this temperature case, highest savings come from the post-1919 flats and the 1950-1983 houses.
The winter peak temperature case results in higher savings than the 20-year peak. This is due to a higher absolute number of suitable homes at increasingly lower flow temperatures in the winter peak case, which uses less stringent suitability criteria.
Savings per year, by archetype (£m) |
Winter peak |
20-year peak | ||
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price | |
Pre-1919 flat |
34.58 |
79.16 |
30.40 |
69.59 |
Pre-1919 house |
9.19 |
21.03 |
7.16 |
16.39 |
1919-2002 flat |
64.40 |
147.40 |
60.70 |
138.94 |
1919-1949 house |
12.95 |
29.63 |
11.38 |
26.04 |
1950-1983 house |
47.85 |
109.52 |
41.44 |
94.85 |
1984-2002 house |
26.01 |
59.54 |
23.62 |
54.06 |
Post-2002 |
23.92 |
54.75 |
23.48 |
53.75 |
Table 5 Potential for fuel bill savings (£m/yr) in peak external temperature cases when all suitable dwellings reduce flow temperatures to 55°C, aggregated to the archetype level (Higher cost retrofit scenario)
Savings per year, by dwelling (£) | |||||
Winter peak |
20-year peak | ||||
Average cost to retrofit |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price | |
Pre-1919 flat |
£1331 |
117.43 |
268.78 |
103.23 |
236.28 |
Pre-1919 house |
£4831 |
45.27 |
103.62 |
35.29 |
80.78 |
1919-2002 flat |
£754 |
99.76 |
228.35 |
94.04 |
215.24 |
1919-1949 house |
£2354 |
72.09 |
165.00 |
63.35 |
145.00 |
1950-1983 house |
£2600 |
63.35 |
145.01 |
54.87 |
125.59 |
1984-2002 house |
£2404 |
96.39 |
220.63 |
87.52 |
200.31 |
Post-2002 |
£396 |
59.89 |
137.08 |
58.79 |
134.57 |
Average |
£2096 |
£79.68 |
£182.39 |
£72.14 |
£165.13 |
Table 6 Potential for fuel bill savings in peak external temperature cases when all suitable dwellings reduce flow temperatures to 55°C, on a per dwelling basis (Higher cost retrofit scenario)
When assessed on a per dwelling basis (see Table 6), the archetypes with the highest fuel bill savings include the pre-1919 flats, post-1919 flats and 1984-2002 houses. These all have the highest rates of savings per dwelling as a direct result of their archetypes’ NEED data. The other archetypes have similar savings per archetype, and the pre-1919 houses have the lowest potential savings at the household level.
Table 7 shows the impact of reducing flow temperatures a further 5°C, to 50°C. Estimates for total fuel bill savings are given. Dwellings suitable for reduction beyond 55°C are assigned savings from reducing to 50°C. The range of savings is increased to £181m-£802m (from £151-£624m at 55°C) depending on the temperature case and retrofit scenario.
Savings per year |
Lower cost retrofits |
Higher cost retrofits | ||
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price | |
Winter peak |
£227m |
£519m |
£291m |
£666m |
20-year peak |
£181m |
£414m |
£251m |
£575m |
Winter average |
£318m |
£728m |
£350m |
£802m |
November average |
£347m |
£795m |
£363m |
£831m |
Table 7 Aggregated total fuel bill savings per year for all temperature cases and retrofit scenarios (at both fuel prices) when all suitable dwellings reduce flow temperatures to 50°C
Emissions modelling
At 55°C, dwellings can save between 2.5 kgCO2/year and 5.5 kgCO2/year depending on the archetype. The emissions saving estimate for each archetype is set by applying the archetype’s average annual heat demand to the carbon intensity of natural gas used for residential heating in Scotland. Based on this, the flat archetypes and 1984-2002 houses have the highest potential emissions savings (see Figure 18).
Figure 18 Emission savings when moving from 75°C to 55°C – showing emissions based on 0.184 kgCO2/kWh for natural gas
When aggregated to the archetype level, the potential for emissions savings ranges from 8.10 MtCO2/yr in the 20-year peak to 8.95 MtCO2/yr in the winter peak for higher cost retrofits. The November average and winter average result in higher emissions savings than the winter peak and 20-year peak temperature case (see Table 8). This is expected due to the increasingly stringent suitability criteria meaning that more homes are suitable for reduced flow temperatures in the average cases compared to peak cases. Lower cost retrofits also reduce potential emissions savings, with a range of 6.17 MtCO2/yr (in the 20-year peak temperature case) to 9.96 MtCO2/yr (November average temperature case).
Total savings per year (MtCO2/yr) |
Lower cost retrofits |
Higher cost retrofits |
Winter peak |
7.40 |
8.95 |
20-year peak |
6.17 |
8.10 |
Winter average |
9.54 |
10.00 |
November average |
9.96 |
10.18 |
Table 8 Potential emissions savings across all temperature cases and retrofit scenarios when all suitable dwellings reduce flow temperatures to 55°C
Table 9 shows the potential savings if all dwellings’ flow temperatures are reduced as low as they are suitable after higher cost retrofits are applied. Most savings come from the post-1919 flats, followed by the 1950-1983 houses and pre-1919 flats.
Savings per year, by archetype (MtCO2/yr) |
Winter peak |
20-year peak |
Winter average |
November average |
Pre-1919 flat |
1.41 |
1.24 |
1.56 |
1.57 |
Pre-1919 house |
0.38 |
0.29 |
0.49 |
0.51 |
1919-2002 flat |
2.63 |
2.48 |
2.82 |
2.84 |
1919-1949 house |
0.53 |
0.47 |
0.62 |
0.64 |
1950-1983 house |
1.96 |
1.69 |
2.33 |
2.40 |
1984-2002 house |
1.06 |
0.97 |
1.19 |
1.23 |
Post-2002 |
0.98 |
0.96 |
0.99 |
0.99 |
Table 9 Potential emissions savings in peak external temperature cases when all suitable dwellings reduce flow temperatures to 55°C, aggregated to the archetype level (Higher cost retrofit scenario)
Table 9 shows the breakdown of the emissions savings by archetype for all temperature cases with higher cost retrofits. The pre-1919 house archetype has the lowest potential savings at archetype level while post-1919 flats and 1950-83 houses provide the highest emissions savings.
Table 10 shows the impact of reducing flow temperatures a further 5°C, to 50°C. Dwellings suitable for reduction beyond 55°C are assigned savings from reducing to 50°C. This shows that emissions savings increase at the lower flow temperature.
Savings per year, by archetype (MtCO2/yr) |
Lower cost retrofits |
Higher cost retrofits |
Winter peak |
9.27 |
11.90 |
20-year peak |
7.39 |
10.27 |
Winter average |
13.01 |
14.33 |
November average |
14.19 |
14.85 |
Table 10 Potential emissions savings in all external temperature cases and retrofit scenarios when all suitable dwellings reduce flow temperatures to 50°C
Conclusions
The evidence base for flow temperature reduction
This study finds a strong theoretical case for broad flow temperature reduction in heating systems and suggests that 55°C is a suitable temperature target, which could result in reductions in energy demand and emissions at individual dwelling level.
While previous work and stakeholders suggest many dwellings will be able to run at 55°C without significant retrofitting, we note the importance of assessing suitability with property-by-property specific heat loss calculations. Our study and others use a variety of factors including ancillary component characteristics, building insulation levels and oversizing factors as proxies for a dwelling’s suitability. However, minimum flow temperature potential should be based on a property-level assessment where possible.
Suitability of the Scottish housing stock
This study has found a lower current level of suitability than suggested through the literature review and stakeholder engagement process. We found 15% of the current housing stock would be suitable for reduced flow temperature at present in our winter peak temperature case, which decreases to 7% in the 20-year peak case.
Suitability increases significantly after retrofits, reaching 55% and 76% of the total stock in the winter peak case after lower cost and higher cost retrofits, respectively. In the 20-year peak case, overall stock suitability rises to 41% to 64% after lower cost and higher cost retrofits, respectively.
There is also potential for dwellings to lower flow temperatures below 55°C, potentially into the 30–50°C range (60% of dwellings in the winter peak, higher cost retrofit scenario), given the heat distribution system’s operating regime is properly maintained and sufficient retrofits are undertaken. This may be more straight forward in some dwelling types than others, particularly flats and recent properties.
The most important factor when assessing suitability for flow temperature reduction is setting suitability criteria that adequately captures the needs of occupants. Our two key temperature cases use particularly stringent criteria, requiring that dwellings should be heated to 20°C during the coldest hour of an average or historic year. This is an ambitious goal and not one currently being met by many heating systems operating between 70°C–80°C, as evidenced by the significant portion of homes that could not meet thermal comfort while operating at 75°C in the scenarios modelled in this study. Care should be taken to ensure that suitability is sufficiently, but not overly, stringent.
The other temperature cases tested in this study (winter average and November average) test a dwelling’s ability to meet suitability during a heating hour in average winter temperatures. Significantly larger proportions of dwellings are suitable for low flow temperatures in these cases suggesting that for most of the year, many homes are suitable to run at lower flow temperatures than in our stringent test cases. Exploring the potential for varying flow temperatures throughout the year could be one way to increase the fuel bill and emissions savings overall, only increasing the flow temperature when heat distribution systems need to meet thermal comfort in peak hours.
Varying internal temperatures may also bring more homes into suitability for lower flow temperatures but this was not modelled in this study. If the internal temperature was lowered (for example to 18°C, which is in the healthy living range for healthy, not vulnerable, occupants) during peak heating hours, more homes could be made suitable. In practice, this would imply an acceptance that domestic heating systems are not expected to meet the higher end of thermal comfort during peak heating hours, which is already the case in many dwellings.
Our study suggests some dwelling archetypes will have higher proportions of the stock already suitable at lower temperatures and that these archetypes will also likely be easier to retrofit for flow temperature reductions. These dwellings tended to include flats and post-2002 dwellings. This could be due to multiple factors, including building footprint in the case of the flats and better building regulations which mandate higher levels of efficiency in the newer dwellings.
Conversely, some dwellings are likely to be harder to prepare for flow temperature reduction and will have a smaller proportion of the stock able to transition without retrofits. This study showed the difficulty in transitioning the pre-1919 houses, which are currently unsuitable for 55°C. These are larger, built with solid walls and tend to have undersized heating systems. This means more expensive retrofits will likely be required to support these dwellings in transitioning to lower flow temperatures. Our modelling identifies that after higher cost retrofits than for other dwelling types, almost half of homes in this archetype can reach suitability for reduced flow temperatures to 55°C.
Retrofitting the housing stock
A consistent finding from this study is that across archetypes and scenarios, retrofits significantly improve the proportion of the housing stock suitable for flow temperature reduction. We have found that building envelope retrofits (insulation, window glazing) and ancillary upgrades (pipework, radiators) are complementary in the transition to ZDEH systems. This means that building retrofits could be a reliable way to increase suitability for reduced flow temperatures and, at a later date, ZDEH systems.
To prepare a dwelling for lower flow temperatures, we suggest that building envelope measures are prioritised to reduce the overall energy demand of the home. Where this is not possible (because dwellings are not adequately insulated, for example) ancillary upgrades should be implemented. Radiator upgrades could be implemented, and the same goal of flow temperature reduction could be achieved but this does not improve energy efficiency in the domestic heating system.
Increased budgets for retrofits lead to increased gains in fuel bill and emissions reductions by allowing dwellings to achieve lower flow temperatures. Even the lower cost retrofit packages resulted in significant fuel bill savings (£151m–£580m depending on temperature case and fuel cost) and potential emissions savings (6.17–9.96 MtCO2/year depending on temperature case).
Benefits to flow temperature reduction
Our findings indicate that there is potential for fuel bill and emissions savings across all archetypes. With higher cost retrofits, fuel bill savings from transitioning the stock to lower flow temperatures could total between £198m and £501m depending on the winter temperature case. Emissions savings are suggested to follow the same trends, with potential to save between 8.10 MtCO2/year and 10.18 MtCO2/year (depending on the winter temperature case).
The fuel bill savings and emissions reduction modelling undertaken in this work supports the view that any flow temperature reduction, whether around 55°C or lower, will bring benefits.
Appendices
Stakeholder engagement summary
Targeted stakeholder engagement was carried out to source further quantitative information and qualitative insights from industry experts. Stakeholders were selected due to their expertise on specific areas of interest and practical experience in this area. A summary of the relevance of the organisation and topics discussed for each stakeholder organisation is shown below.
Organisation: Historic Environment Scotland
Relevance: Knowledgeable government agency
Topics discussed:
- Thermal comfort of occupants and building fabric (with an emphasis on maintaining enough ventilation in the dwelling to avoid moisture build-up, resulting in damp and mould).
- Potential to reduce the flow temperature in historically built dwellings (in our study, this means the pre-1919 flats and houses) and what insulation measures might best support this aim.
- Suitability for historically built dwellings to maintain lower internal temperatures than occupants can safely live in, thus suggesting internal temperature is not a concern for the health of the building envelope.
- Potential difficulty in renovating historically built homes, particularly challenges around floor insulation and double/triple window glazing.
- Benefits to lowering flow temperatures and heating the house more gradually.
Organisation: Heat Pump Association
Relevance: Industry organisation
Topics discussed:
- Confirmation of HPA’s assertion that 55°C is the “target” flow temperature for all dwellings, and reasoning behind this (discussion around 55°C as the “compromise” between the increased efficiency of boilers at lower flow temperatures and heat pumps’ ability to operate efficiently at up to approximately this temperature).
- The trade-off between benefits of reduced flow temperature and increasingly stringent requirements for air tightness and increased energy efficiency measures in the dwelling, which also played a role in HPA’s selection of a “target” flow temperature.
- Discussion of risks of legionella, and components of heat pumps which will guard against legionella risk (including a broader discussion on factors causing legionella).
Organisation: Renewable Heat
Relevance: Heat pump installation specialists
Topics discussed:
- Potentially for the Scottish housing stock to reduce flow temperature, based on experience and monitoring efforts by renewable heat (this include a conversation regarding how to best consider whether dwellings might be suitable for flow temperature reduction based on their type and age, then being further segmented by insulation measures and specific heat loss rates).
- Discussion around credibility of HPA’s target flow temperature across homes, which Renewable Heat thought was a generally sound target.
- Discussion around potential to reduce flow temperature beyond 55°C, and the difficult of preparing the housing stock for temperatures this low, including what potential considerations may need to be taken for various dwellings, particularly the historically built dwellings.
- Rules of thumbs for what heat loss rates are required for reducing the flow temperature in 5°C increments, and at what point underfloor heating would be required regardless of building envelope and a low heat loss rate, based on the company’s installations.
- Potential for pipework replacement required as part of ancillary upgrades to the dwelling due to pipes with smaller diameters being common in the late 20th century (this would be relevant if the flow rate of the heat distribution system needed to be increased to improve heat transfer).
Organisation: Ovo Energy
Relevance: Energy company, heat pump trial participant
Topics discussed:
- Potential for boiler and heat pump systems to reach flow temperatures of 55°C or lower, and the difference in low temperature versus high temperature units.
- Impact of refrigerant type on heating system performance.
- Importance of prioritising building envelope retrofits to increase energy efficiency as a means of overall energy use reduction.
- Potential oversizing of radiators in the housing stock today.
- Importance of retrofitting the dwelling before/as the heat system or ancillary components are being replaced, to avoid an unnecessarily large oversizing factor.
- Ability for homes with heat pumps and lower flow temperatures to meet thermal comfort, with discussion of case studies in cold-weather climates (i.e., Scandinavia).
Organisation: Energy Saving Trust
Relevance: Knowledgeable company
Topics discussed:
- Validation of topics discussed in above stakeholder engagement.
- Potential oversizing of radiators in the housing stock today.
- Building envelope efficiency measures versus ancillary component (mainly radiators) upgrades for flow temperature reduction.
- Importance of prioritising overall energy efficiency over ancillary upgrades as a means of overall energy use reduction (and the importance of preparing the stock for flow temperature reduction as a means of achieving other goals such as overall energy reduction, decarbonisation, etc.).
Peak external temperature cases
In this study, we used external temperature cases assigned to specific properties from previous analysis for BEIS (Element Energy, 2021) to inform oversizing factors for heating systems. Oversizing factors for properties, which included the relationship between peak external temperature and radiator capacity, were used instead of assigning specific peak external temperatures to each home. Homes are not explicitly assigned peak external temperatures because this would require granular data about the heat system capacity of individual homes, which was not available in the HAS data.
The temperatures in the original modelling (Element Energy, 2021) are more akin to Scottish central belt temperatures. The external temperatures from the original study would not be an accurate reflection of average Scottish temperatures across the whole country, so were not used in this work. Instead, we extrapolated the relationship between external temperature and the ability for heat systems to meet demand in homes.
These temperatures, and the distribution of homes they were applied to in the original BEIS modelling, were used with other factors, e.g., heat system capacity, to determine oversizing factors under different external temperature cases to determine suitability for lower flow temperatures.
Although specific external temperatures were not used directly in this work, the approximate temperatures represented by the four external temperature cases would be in the order of:
- Winter peak: around 0 to -10°C
- 20-year peak: around -10 to -20°C
- Winter average: around 1 to 3°C
- November average: around 3 to 5°C
Retrofit package data
Retrofit Package |
Average cost (£, flat) |
Efficiency increase |
Cost per marginal increase to efficiency (£/% efficiency gained) |
Average cost (£, houses) |
Efficiency Increase |
Cost per marginal increase to efficiency (£/% efficiency gained) |
Loft and cavity wall insulation |
£1003.48 |
35% |
£28.67 |
£1521.65 |
24% |
£63.40 |
Loft (partial) and cavity wall insulation |
£1003.48 |
23% |
£43.63 |
£1521.65 |
17% |
£89.51 |
Hard to treat (HTT) cavity wall insulation |
£1989.30 |
28% |
£71.05 |
£3427.56 |
19% |
£180.40 |
HTT loft and cavity wall insulation |
£1529.81 |
35% |
£43.71 |
£1751.11 |
22% |
£79.60 |
HTT loft insulation |
£1100.20 |
23% |
£47.83 |
£1174.38 |
14% |
£83.88 |
Standard efficiency measures[1] |
£176.20 |
13% |
£13.55 |
£361.88 |
10% |
£36.19 |
Radiator upgrades (<90m) |
£2206.10 |
Oversizing factor doubles |
– |
£2206.10 |
Oversizing factor doubles |
– |
Cavity wall, loft and floor insulation |
£3924.94 |
45% |
£87.22 |
£4323.97 |
33% |
£131.03 |
Cavity wall, loft and floor insulation with radiator upgrade |
– |
– |
– |
£7633.16 |
24%+ Oversizing factor doubles |
£318.05 |
Loft and floor insulation |
£3495.33 |
29% |
£120.53 |
£5410.75 |
24% |
£225.45 |
Solid wall and loft insulation |
£2979.05 |
37% |
£80.51 |
£5766.00 |
28% |
£205.93 |
Solid walls, loft and floor insulation |
£5900.51 |
48% |
£122.93 |
£8253.73 |
37% |
£223.07 |
Building-envelope led method for suitability assessment
A central finding from our stakeholder engagement is the estimation of a dwelling’s suitability based on a combination of the dwelling’s building envelope (i.e., levels of various insulation) and peak heat demand. This approach is based on the following principle:
- In pre-1919 dwellings (flats and houses), operating at 55°C is possible with double/triple window glazing, loft insulation of at least 100mm and draughtproofing measures.
- In flats, operating at 55°C is possible with double/triple window glazing and wall insulation. These conditions are the same to operate at 50°C (only achievable in homes built after 1984) and 45°C (only achievable in homes built after 1992).
- In houses, operating at 55°C is possible with double/triple window glazing, loft insulation of at least 100mm and wall insulation. To run at lower temperatures, houses must have 250mm of loft insulation and floor insulation. Temperatures below 45°C are not suitable without underfloor heating or a heat demand threshold below 45Wm2.
Based on this, dwellings could be roughly designated a minimum flow temperature based on their archetype and insulation levels. See below for an estimate of what dwellings are considered always suitable (green – always), suitable depending on insulation measures (yellow – depends) and unsuitable without underfloor heating or peak heat demand below 45W/m2 (red – unsuitable).
55°C |
50°C |
45°C |
40°C |
35°C | |
Pre-1919 flat |
sometimes |
unsuitable |
unsuitable |
unsuitable |
unsuitable |
Pre-1919 house |
sometimes |
unsuitable |
unsuitable |
unsuitable |
unsuitable |
’19-’02 flat |
sometimes |
sometimes |
sometimes |
unsuitable |
unsuitable |
’19-’49 house |
sometimes |
sometimes |
sometimes |
unsuitable |
unsuitable |
’50-’83 house |
sometimes |
sometimes |
sometimes |
unsuitable |
unsuitable |
’84-’02 house |
sometimes |
sometimes |
sometimes |
unsuitable |
unsuitable |
Post-‘02 flats and houses |
always |
always |
sometimes |
unsuitable |
unsuitable |
The results of our modelling generally agree with the finding that all dwelling types could, in theory, reach lower flow temperatures (45 – 55°C). Our study additionally finds that many dwellings in all archetypes, after some level of retrofits, could operate at even lower flow temperatures (35 – 45°C). This contrasts the stakeholders’ assumptions that for older dwelling types these low temperatures may not be attainable. It is important to note that while this approach was discussed with us by stakeholders with ample experience in home retrofitting, it is not backed by any quantitative study and as such may best be considered as “robust rules of thumbs”. In practice, dwelling suitability should be based on a quantitative assessment undertaken at the property level.
Detailed results – suitability modelling
Winter peak – suitability now (all winter peak scenarios)
Number of dwellings suitable at each flow temperature, by archetype | |||||||
Pre-1919 flat |
Pre-1919 house |
1919-2002 flat |
1919-1949 house |
1950-1983 house |
1984-2002 house |
Post-2002 | |
30°C |
– |
– |
– |
– |
– |
– |
– |
35°C |
– |
– |
– |
– |
– |
– |
– |
40°C |
– |
– |
13,129 |
– |
– |
– |
555 |
45°C |
– |
– |
34,106 |
– |
5,140 |
6,127 |
7,851 |
50°C |
– |
– |
86,664 |
2,740 |
17,290 |
6,127 |
38,145 |
55°C |
12,515 |
– |
193,456 |
12,718 |
63,901 |
18,180 |
107,716 |
60°C |
34,830 |
13,479 |
323,560 |
40,452 |
184,780 |
74,660 |
188,503 |
65°C |
105,485 |
35,131 |
409,306 |
87,930 |
347,068 |
167,539 |
246,342 |
70°C |
183,445 |
60,266 |
494,218 |
108,147 |
505,634 |
204,541 |
358,035 |
75°C |
212,125 |
102,801 |
566,410 |
129,864 |
601,460 |
216,426 |
375,979 |
80°C |
253,320 |
122,005 |
589,514 |
144,744 |
670,749 |
229,331 |
392,185 |
85°C |
273,917 |
154,294 |
608,833 |
152,820 |
712,624 |
241,216 |
392,185 |
90°C |
294,515 |
202,925 |
645,503 |
179,580 |
755,251 |
269,874 |
399,419 |
Winter peak – Lower cost retrofit scenario
Number of dwellings suitable at each flow temperature, by archetype | |||||||
Pre-1919 flat |
Pre-1919 house |
1919-2002 flat |
1919-1949 house |
1950-1983 house |
1984-2002 house |
Post-2002 | |
30°C |
– |
– |
– |
– |
– |
– |
– |
35°C |
– |
– |
13,929 |
– |
– |
– |
448 |
40°C |
– |
– |
85,543 |
– |
17,960 |
286 |
17,143 |
45°C |
6,350 |
– |
268,355 |
14,754 |
79,266 |
17,672 |
85,326 |
50°C |
88,836 |
1,837 |
396,258 |
38,466 |
236,930 |
72,603 |
158,850 |
55°C |
138,703 |
12,591 |
522,090 |
60,495 |
377,385 |
126,057 |
267,161 |
60°C |
200,687 |
33,866 |
575,252 |
100,921 |
502,890 |
162,693 |
294,799 |
65°C |
244,355 |
63,463 |
611,965 |
129,972 |
609,035 |
206,203 |
349,079 |
70°C |
272,197 |
104,343 |
631,749 |
146,453 |
670,055 |
214,351 |
390,531 |
75°C |
279,739 |
130,707 |
640,352 |
154,715 |
705,860 |
227,956 |
397,162 |
80°C |
291,369 |
156,971 |
643,239 |
162,089 |
737,202 |
241,242 |
399,267 |
85°C |
292,231 |
178,000 |
644,254 |
170,539 |
748,796 |
241,553 |
399,419 |
90°C |
294,515 |
202,925 |
645,503 |
179,580 |
755,251 |
269,874 |
399,419 |
Winter peak – Higher cost retrofit scenario
Number of dwellings suitable at each flow temperature, by archetype | |||||||
Pre-1919 flat |
Pre-1919 house |
1919-2002 flat |
1919-1949 house |
1950-1983 house |
1984-2002 house |
Post-2002 | |
30°C |
– |
– |
– |
– |
– |
– |
– |
35°C |
– |
– |
21,939 |
– |
– |
3,962 |
7,703 |
40°C |
– |
– |
126,863 |
3,765 |
14,154 |
10,084 |
53,145 |
45°C |
35,813 |
7,774 |
338,881 |
46,074 |
139,737 |
64,469 |
211,578 |
50°C |
150,202 |
45,992 |
487,979 |
89,093 |
351,768 |
145,208 |
350,313 |
55°C |
239,712 |
94,330 |
555,898 |
121,505 |
497,471 |
186,626 |
386,730 |
60°C |
269,706 |
143,666 |
592,894 |
146,453 |
611,384 |
221,411 |
396,474 |
65°C |
278,537 |
169,788 |
627,336 |
159,300 |
667,660 |
236,768 |
398,483 |
70°C |
291,168 |
181,024 |
637,547 |
167,637 |
714,021 |
240,638 |
399,009 |
75°C |
293,226 |
184,379 |
640,342 |
171,366 |
729,163 |
245,907 |
399,398 |
80°C |
294,362 |
186,921 |
642,979 |
175,204 |
743,553 |
246,189 |
399,419 |
85°C |
294,373 |
188,866 |
643,767 |
177,725 |
744,431 |
247,343 |
399,419 |
90°C |
294,515 |
202,925 |
645,503 |
179,580 |
755,251 |
269,874 |
399,419 |
Winter peak – Lower cost retrofit scenario (reduced radiators)
Number of dwellings suitable at each flow temperature, by archetype | |||||||
Pre-1919 flat |
Pre-1919 house |
1919-2002 flat |
1919-1949 house |
1950-1983 house |
1984-2002 house |
Post-2002 | |
30°C |
– |
– |
– |
– |
– |
– |
– |
35°C |
– |
– |
1,329 |
– |
– |
– |
– |
40°C |
– |
– |
14,037 |
– |
– |
286 |
715 |
45°C |
– |
– |
42,023 |
– |
5,392 |
6,127 |
12,162 |
50°C |
2,370 |
– |
104,575 |
3,997 |
25,527 |
10,324 |
49,899 |
55°C |
18,455 |
5,567 |
221,982 |
21,846 |
110,092 |
55,507 |
178,177 |
60°C |
57,730 |
23,398 |
363,690 |
65,526 |
240,279 |
103,306 |
207,535 |
65°C |
123,510 |
51,429 |
431,606 |
103,900 |
417,431 |
176,704 |
294,268 |
70°C |
192,207 |
90,725 |
508,913 |
125,326 |
544,019 |
205,708 |
368,677 |
75°C |
223,714 |
122,276 |
571,891 |
138,338 |
627,757 |
227,956 |
383,521 |
80°C |
268,439 |
148,540 |
594,523 |
153,263 |
703,624 |
241,242 |
393,314 |
85°C |
275,900 |
173,013 |
612,117 |
161,749 |
715,272 |
241,553 |
393,466 |
90°C |
294,515 |
202,925 |
645,503 |
179,580 |
755,251 |
269,874 |
399,419 |
Winter peak – Higher cost retrofit scenario (reduced radiators)
Number of dwellings suitable at each flow temperature, by archetype | |||||||
Pre-1919 flat |
Pre-1919 house |
1919-2002 flat |
1919-1949 house |
1950-1983 house |
1984-2002 house |
Post-2002 | |
30°C |
– |
– |
– |
– |
– |
– |
– |
35°C |
– |
– |
6,987 |
– |
– |
– |
1 |
40°C |
– |
– |
15,849 |
87 |
913 |
2,165 |
593 |
45°C |
1,063 |
2,492 |
70,646 |
1,592 |
12,615 |
7,618 |
16,437 |
50°C |
16,556 |
17,687 |
154,457 |
13,474 |
65,705 |
22,975 |
56,313 |
55°C |
50,676 |
45,554 |
276,700 |
38,557 |
191,423 |
77,426 |
183,423 |
60°C |
92,093 |
79,999 |
418,668 |
84,958 |
353,694 |
140,440 |
219,451 |
65°C |
182,336 |
113,544 |
497,086 |
116,029 |
526,282 |
202,213 |
313,225 |
70°C |
220,030 |
142,140 |
562,040 |
134,671 |
623,564 |
212,776 |
367,606 |
75°C |
261,756 |
156,948 |
592,909 |
149,802 |
681,262 |
233,959 |
392,427 |
80°C |
277,857 |
173,271 |
602,469 |
157,048 |
719,032 |
242,036 |
392,448 |
85°C |
284,142 |
181,786 |
617,125 |
166,516 |
725,504 |
243,190 |
399,419 |
90°C |
294,515 |
202,925 |
645,503 |
179,580 |
755,251 |
269,874 |
399,419 |
20-year peak – suitability now (all 20-year peak scenarios)
Number of dwellings suitable at each flow temperature, by archetype | |||||||
Pre-1919 flat |
Pre-1919 house |
1919-2002 flat |
1919-1949 house |
1950-1983 house |
1984-2002 house |
Post-2002 | |
30°C |
– |
– |
– |
– |
– |
– |
– |
35°C |
– |
– |
– |
– |
– |
– |
– |
40°C |
– |
– |
13,129 |
– |
– |
– |
555 |
45°C |
– |
– |
14,444 |
– |
– |
– |
555 |
50°C |
– |
– |
54,596 |
– |
5,140 |
6,127 |
8,406 |
55°C |
– |
– |
105,604 |
2,740 |
22,542 |
12,254 |
45,441 |
60°C |
12,515 |
– |
228,970 |
20,739 |
107,372 |
23,603 |
128,535 |
65°C |
22,315 |
17,972 |
316,995 |
45,930 |
187,124 |
80,295 |
197,983 |
70°C |
76,024 |
30,638 |
417,764 |
82,508 |
307,202 |
142,242 |
272,028 |
75°C |
158,415 |
55,772 |
500,781 |
106,332 |
481,949 |
193,477 |
329,359 |
80°C |
199,611 |
94,005 |
550,970 |
122,626 |
563,482 |
217,446 |
375,979 |
85°C |
248,888 |
118,332 |
578,322 |
135,690 |
634,460 |
229,331 |
375,979 |
90°C |
294,515 |
202,925 |
645,503 |
179,580 |
755,251 |
269,874 |
399,419 |
20-year peak – Lower cost retrofit scenario
Number of dwellings suitable at each flow temperature, by archetype | |||||||
Pre-1919 flat |
Pre-1919 house |
1919-2002 flat |
1919-1949 house |
1950-1983 house |
1984-2002 house |
Post-2002 | |
30°C |
– |
– |
– |
– |
– |
– |
– |
35°C |
– |
– |
12,037 |
– |
– |
– |
448 |
40°C |
– |
– |
57,454 |
– |
4,059 |
– |
555 |
45°C |
– |
– |
180,145 |
6,081 |
43,583 |
6,127 |
61,474 |
50°C |
25,738 |
1,837 |
322,225 |
23,349 |
131,382 |
33,777 |
123,861 |
55°C |
89,909 |
1,837 |
447,529 |
43,689 |
272,703 |
71,987 |
189,548 |
60°C |
169,371 |
20,207 |
524,233 |
67,770 |
410,699 |
118,243 |
269,896 |
65°C |
206,907 |
31,536 |
580,993 |
98,510 |
502,766 |
155,102 |
311,011 |
70°C |
245,626 |
62,757 |
604,261 |
124,745 |
588,437 |
206,869 |
322,107 |
75°C |
261,437 |
98,199 |
631,868 |
139,249 |
656,151 |
222,692 |
385,489 |
80°C |
277,752 |
126,318 |
639,831 |
150,072 |
692,811 |
229,368 |
391,736 |
85°C |
281,481 |
142,554 |
641,828 |
156,617 |
723,820 |
230,006 |
399,205 |
90°C |
294,515 |
202,925 |
645,503 |
179,580 |
755,251 |
269,874 |
399,419 |
20-year peak – Higher cost retrofit scenario
Number of dwellings suitable at each flow temperature, by archetype | |||||||
Pre-1919 flat |
Pre-1919 house |
1919-2002 flat |
1919-1949 house |
1950-1983 house |
1984-2002 house |
Post-2002 | |
30°C |
– |
– |
– |
– |
– |
– |
– |
35°C |
– |
– |
13,024 |
– |
– |
– |
554 |
40°C |
– |
– |
76,118 |
1,872 |
10,598 |
4,485 |
29,868 |
45°C |
15,146 |
1,829 |
221,053 |
15,637 |
78,297 |
20,744 |
147,464 |
50°C |
91,229 |
25,806 |
380,846 |
62,467 |
237,061 |
121,390 |
273,859 |
55°C |
177,740 |
60,940 |
505,511 |
98,484 |
388,291 |
159,045 |
368,331 |
60°C |
241,697 |
105,701 |
570,990 |
124,025 |
518,556 |
189,663 |
394,570 |
65°C |
271,720 |
139,737 |
589,884 |
148,256 |
615,544 |
227,994 |
397,189 |
70°C |
277,320 |
164,168 |
622,390 |
158,597 |
665,440 |
236,466 |
398,256 |
75°C |
291,154 |
179,683 |
637,448 |
165,030 |
706,443 |
240,775 |
399,159 |
80°C |
293,143 |
183,872 |
639,035 |
169,908 |
726,531 |
243,417 |
399,353 |
85°C |
293,277 |
185,024 |
642,234 |
172,430 |
742,425 |
246,180 |
399,419 |
90°C |
294,515 |
202,925 |
645,503 |
179,580 |
755,251 |
269,874 |
399,419 |
20-year peak – Lower cost retrofit scenario (reduced radiators)
Number of dwellings suitable at each flow temperature, by archetype | |||||||
Pre-1919 flat |
Pre-1919 house |
1919-2002 flat |
1919-1949 house |
1950-1983 house |
1984-2002 house |
Post-2002 | |
30°C |
– |
– |
– |
– |
– |
– |
– |
35°C |
– |
– |
609 |
– |
– |
– |
– |
40°C |
– |
– |
13,265 |
– |
– |
– |
555 |
45°C |
– |
– |
19,145 |
– |
664 |
6,127 |
1,007 |
50°C |
– |
– |
66,232 |
592 |
7,764 |
6,137 |
20,206 |
55°C |
3,443 |
– |
127,154 |
6,816 |
39,808 |
12,969 |
53,236 |
60°C |
19,352 |
13,183 |
254,896 |
31,096 |
142,446 |
51,201 |
184,041 |
65°C |
48,638 |
22,914 |
354,533 |
63,779 |
242,819 |
97,188 |
217,794 |
70°C |
128,226 |
50,723 |
438,192 |
100,538 |
391,214 |
172,370 |
280,139 |
75°C |
181,741 |
84,581 |
514,346 |
116,896 |
523,864 |
207,288 |
365,533 |
80°C |
211,104 |
117,796 |
557,819 |
133,644 |
601,360 |
220,725 |
378,095 |
85°C |
255,227 |
134,123 |
583,512 |
144,201 |
671,898 |
230,006 |
385,564 |
90°C |
294,515 |
202,925 |
645,503 |
179,580 |
755,251 |
269,874 |
399,419 |
20-year peak – Higher cost retrofit scenario (reduced radiators)
Number of dwellings suitable at each flow temperature, by archetype | |||||||
Pre-1919 flat |
Pre-1919 house |
1919-2002 flat |
1919-1949 house |
1950-1983 house |
1984-2002 house |
Post-2002 | |
30°C |
– |
– |
– |
– |
– |
– |
– |
35°C |
– |
– |
956 |
– |
– |
– |
– |
40°C |
– |
– |
13,864 |
– |
256 |
523 |
555 |
45°C |
– |
– |
29,249 |
367 |
6,682 |
6,643 |
985 |
50°C |
3,876 |
9,876 |
85,108 |
4,348 |
29,327 |
11,702 |
31,235 |
55°C |
19,995 |
22,538 |
197,209 |
18,427 |
86,152 |
28,297 |
86,749 |
60°C |
59,090 |
55,685 |
291,025 |
46,036 |
216,619 |
84,547 |
191,293 |
65°C |
94,107 |
79,360 |
409,352 |
84,303 |
361,875 |
150,122 |
256,425 |
70°C |
181,119 |
107,924 |
477,443 |
108,119 |
510,680 |
199,635 |
282,937 |
75°C |
215,638 |
138,819 |
551,689 |
130,257 |
591,746 |
221,428 |
376,509 |
80°C |
258,269 |
155,035 |
581,920 |
142,190 |
665,691 |
231,469 |
376,703 |
85°C |
268,436 |
162,505 |
606,729 |
150,866 |
710,271 |
234,232 |
399,419 |
90°C |
294,515 |
202,925 |
645,503 |
179,580 |
755,251 |
269,874 |
399,419 |
Winter average – suitability now (all winter average scenarios)
Number of dwellings suitable at each flow temperature, by archetype | |||||||
Pre-1919 flat |
Pre-1919 house |
1919-2002 flat |
1919-1949 house |
1950-1983 house |
1984-2002 house |
Post-2002 | |
30°C |
– |
– |
– |
– |
– |
– |
– |
35°C |
– |
– |
13,129 |
– |
– |
– |
555 |
40°C |
– |
– |
43,403 |
– |
5,140 |
6,127 |
8,406 |
45°C |
– |
– |
164,293 |
2,740 |
22,542 |
12,254 |
92,631 |
50°C |
22,315 |
13,479 |
345,944 |
38,691 |
178,163 |
74,660 |
188,503 |
55°C |
158,415 |
39,624 |
471,833 |
100,071 |
413,283 |
177,603 |
286,237 |
60°C |
212,125 |
89,893 |
559,845 |
128,103 |
590,790 |
204,541 |
375,979 |
65°C |
261,403 |
125,677 |
592,248 |
142,005 |
670,749 |
229,331 |
392,185 |
70°C |
282,000 |
158,787 |
608,833 |
160,114 |
717,763 |
241,216 |
399,419 |
75°C |
282,000 |
179,230 |
628,152 |
172,008 |
723,294 |
247,343 |
399,419 |
80°C |
294,515 |
182,903 |
638,938 |
172,008 |
729,351 |
247,343 |
399,419 |
85°C |
294,515 |
187,396 |
645,503 |
176,840 |
744,016 |
247,343 |
399,419 |
90°C |
294,515 |
202,925 |
645,503 |
179,580 |
755,251 |
269,874 |
399,419 |
Winter average – Lower cost retrofit scenario
Number of dwellings suitable at each flow temperature, by archetype | |||||||
Pre-1919 flat |
Pre-1919 house |
1919-2002 flat |
1919-1949 house |
1950-1983 house |
1984-2002 house |
Post-2002 | |
30°C |
– |
– |
5,832 |
– |
– |
– |
– |
35°C |
– |
– |
76,561 |
– |
4,059 |
– |
16,578 |
40°C |
16,985 |
– |
319,867 |
17,798 |
86,087 |
21,162 |
92,186 |
45°C |
134,034 |
3,467 |
481,831 |
44,556 |
320,833 |
79,733 |
206,680 |
50°C |
208,772 |
28,919 |
586,587 |
98,834 |
494,791 |
151,135 |
294,401 |
55°C |
259,944 |
77,714 |
630,357 |
133,708 |
638,844 |
209,884 |
383,903 |
60°C |
281,481 |
126,350 |
640,332 |
152,426 |
700,839 |
218,527 |
390,948 |
65°C |
292,111 |
152,714 |
643,667 |
163,833 |
742,252 |
241,242 |
399,373 |
70°C |
293,420 |
182,550 |
644,688 |
171,069 |
749,369 |
245,613 |
399,419 |
75°C |
294,515 |
186,111 |
645,302 |
176,277 |
751,508 |
247,343 |
399,419 |
80°C |
294,515 |
190,566 |
645,503 |
178,506 |
752,960 |
258,925 |
399,419 |
85°C |
294,515 |
190,566 |
645,503 |
179,383 |
753,762 |
258,925 |
399,419 |
90°C |
294,515 |
202,925 |
645,503 |
179,580 |
755,251 |
269,874 |
399,419 |
Winter average – Higher cost retrofit scenario
Number of dwellings suitable at each flow temperature, by archetype | |||||||
Pre-1919 flat |
Pre-1919 house |
1919-2002 flat |
1919-1949 house |
1950-1983 house |
1984-2002 house |
Post-2002 | |
30°C |
– |
– |
11,499 |
– |
– |
– |
– |
35°C |
– |
– |
102,461 |
1,872 |
10,755 |
4,754 |
43,940 |
40°C |
55,082 |
14,483 |
363,366 |
50,096 |
175,705 |
95,833 |
240,776 |
45°C |
211,162 |
73,999 |
537,510 |
108,094 |
434,246 |
157,876 |
368,809 |
50°C |
271,410 |
136,115 |
594,714 |
145,663 |
609,595 |
218,739 |
396,551 |
55°C |
291,030 |
171,706 |
629,353 |
161,994 |
682,087 |
237,154 |
398,847 |
60°C |
293,143 |
183,798 |
639,544 |
169,888 |
725,973 |
243,416 |
399,398 |
65°C |
294,362 |
188,456 |
642,917 |
176,031 |
743,553 |
246,180 |
399,419 |
70°C |
294,427 |
192,752 |
645,020 |
177,831 |
745,902 |
247,343 |
399,419 |
75°C |
294,515 |
195,843 |
645,503 |
178,463 |
750,535 |
257,387 |
399,419 |
80°C |
294,515 |
197,806 |
645,503 |
179,108 |
752,284 |
257,475 |
399,419 |
85°C |
294,515 |
197,868 |
645,503 |
179,580 |
754,121 |
258,921 |
399,419 |
90°C |
294,515 |
202,925 |
645,503 |
179,580 |
755,251 |
269,874 |
399,419 |
Winter average – Lower cost retrofit scenario (reduced radiators)
Number of dwellings suitable at each flow temperature, by archetype | |||||||
Pre-1919 flat |
Pre-1919 house |
1919-2002 flat |
1919-1949 house |
1950-1983 house |
1984-2002 house |
Post-2002 | |
30°C |
– |
– |
– |
– |
– |
– |
– |
35°C |
– |
– |
13,352 |
– |
– |
– |
555 |
40°C |
– |
– |
54,024 |
– |
5,426 |
6,127 |
19,022 |
45°C |
13,786 |
47 |
184,797 |
6,992 |
71,422 |
13,954 |
111,278 |
50°C |
50,503 |
20,297 |
385,831 |
64,137 |
227,471 |
91,748 |
207,137 |
55°C |
180,248 |
64,096 |
487,289 |
109,501 |
490,093 |
187,461 |
329,092 |
60°C |
225,456 |
116,055 |
566,399 |
134,879 |
614,570 |
209,884 |
377,307 |
65°C |
275,780 |
144,283 |
597,323 |
151,238 |
703,643 |
241,242 |
393,420 |
70°C |
283,309 |
175,894 |
612,551 |
165,419 |
719,769 |
245,613 |
399,419 |
75°C |
284,404 |
181,357 |
629,704 |
172,987 |
726,006 |
247,343 |
399,419 |
80°C |
294,515 |
187,396 |
639,442 |
175,216 |
732,190 |
247,343 |
399,419 |
85°C |
294,515 |
187,396 |
645,503 |
177,454 |
744,437 |
247,343 |
399,419 |
90°C |
294,515 |
202,925 |
645,503 |
179,580 |
755,251 |
269,874 |
399,419 |
Winter average – Higher cost retrofit scenario (reduced radiators)
Number of dwellings suitable at each flow temperature, by archetype | |||||||
Pre-1919 flat |
Pre-1919 house |
1919-2002 flat |
1919-1949 house |
1950-1983 house |
1984-2002 house |
Post-2002 | |
30°C |
– |
– |
37 |
– |
– |
– |
– |
35°C |
– |
– |
14,310 |
– |
413 |
792 |
555 |
40°C |
3,876 |
3,733 |
74,968 |
2,427 |
16,336 |
8,802 |
23,910 |
45°C |
38,788 |
29,944 |
235,488 |
26,544 |
132,227 |
39,012 |
116,727 |
50°C |
103,542 |
75,549 |
420,488 |
84,111 |
346,882 |
141,440 |
219,528 |
55°C |
209,225 |
120,491 |
535,920 |
118,723 |
559,708 |
209,292 |
367,444 |
60°C |
268,302 |
156,367 |
592,111 |
145,215 |
664,080 |
226,177 |
376,748 |
65°C |
284,131 |
171,250 |
611,969 |
157,875 |
719,032 |
242,027 |
399,419 |
70°C |
284,196 |
184,342 |
629,838 |
168,989 |
726,975 |
247,343 |
399,419 |
75°C |
294,515 |
189,058 |
639,745 |
173,226 |
735,245 |
247,343 |
399,419 |
80°C |
294,515 |
192,983 |
645,503 |
177,165 |
745,039 |
247,431 |
399,419 |
85°C |
294,515 |
193,045 |
645,503 |
177,637 |
746,876 |
248,877 |
399,419 |
90°C |
294,515 |
202,925 |
645,503 |
179,580 |
755,251 |
269,874 |
399,419 |
November average – suitability now (all November average scenarios)
Number of dwellings suitable at each flow temperature, by archetype | |||||||
Pre-1919 flat |
Pre-1919 house |
1919-2002 flat |
1919-1949 house |
1950-1983 house |
1984-2002 house |
Post-2002 | |
30°C |
– |
– |
– |
– |
– |
– |
– |
35°C |
– |
– |
13,849 |
– |
– |
– |
555 |
40°C |
– |
– |
86,664 |
– |
5,140 |
6,127 |
38,145 |
45°C |
22,315 |
8,986 |
261,790 |
20,739 |
134,879 |
57,977 |
188,503 |
50°C |
150,332 |
35,131 |
469,099 |
87,930 |
408,143 |
183,027 |
255,822 |
55°C |
232,722 |
94,195 |
571,037 |
128,103 |
590,790 |
204,541 |
375,979 |
60°C |
269,486 |
125,677 |
608,833 |
148,264 |
700,473 |
241,216 |
392,185 |
65°C |
282,000 |
171,255 |
614,226 |
163,199 |
723,294 |
241,216 |
399,419 |
70°C |
294,515 |
182,903 |
638,938 |
172,008 |
729,351 |
247,343 |
399,419 |
75°C |
294,515 |
187,396 |
645,503 |
176,840 |
737,959 |
247,343 |
399,419 |
80°C |
294,515 |
187,396 |
645,503 |
176,840 |
744,016 |
247,343 |
399,419 |
85°C |
294,515 |
187,396 |
645,503 |
179,580 |
749,721 |
247,343 |
399,419 |
90°C |
294,515 |
202,925 |
645,503 |
179,580 |
755,251 |
269,874 |
399,419 |
November average – Lower cost retrofit scenario
Number of dwellings suitable at each flow temperature, by archetype | |||||||
Pre-1919 flat |
Pre-1919 house |
1919-2002 flat |
1919-1949 house |
1950-1983 house |
1984-2002 house |
Post-2002 | |
30°C |
– |
– |
11,984 |
– |
– |
– |
448 |
35°C |
– |
– |
151,542 |
3,765 |
18,624 |
6,127 |
58,345 |
40°C |
88,836 |
1,837 |
415,895 |
34,983 |
220,724 |
67,864 |
151,771 |
45°C |
192,928 |
21,839 |
567,126 |
80,194 |
452,326 |
140,407 |
282,866 |
50°C |
259,944 |
77,581 |
620,344 |
132,779 |
618,576 |
209,823 |
384,278 |
55°C |
281,481 |
129,106 |
640,332 |
153,575 |
703,684 |
222,459 |
392,421 |
60°C |
292,231 |
164,426 |
643,687 |
168,170 |
743,641 |
241,242 |
399,419 |
65°C |
293,420 |
183,421 |
645,302 |
175,048 |
749,764 |
247,343 |
399,419 |
70°C |
294,515 |
189,267 |
645,503 |
176,521 |
752,199 |
258,925 |
399,419 |
75°C |
294,515 |
190,566 |
645,503 |
179,307 |
753,730 |
258,925 |
399,419 |
80°C |
294,515 |
191,371 |
645,503 |
179,580 |
754,709 |
258,925 |
399,419 |
85°C |
294,515 |
192,752 |
645,503 |
179,580 |
755,251 |
258,971 |
399,419 |
90°C |
294,515 |
202,925 |
645,503 |
179,580 |
755,251 |
269,874 |
399,419 |
November average – Higher cost retrofit scenario
Number of dwellings suitable at each flow temperature, by archetype | |||||||
Pre-1919 flat |
Pre-1919 house |
1919-2002 flat |
1919-1949 house |
1950-1983 house |
1984-2002 house |
Post-2002 | |
30°C |
– |
– |
11,846 |
– |
– |
– |
554 |
35°C |
8,717 |
– |
191,671 |
9,096 |
53,444 |
16,839 |
112,958 |
40°C |
159,005 |
41,003 |
495,297 |
82,547 |
334,873 |
143,283 |
367,608 |
45°C |
268,029 |
122,898 |
586,338 |
136,328 |
568,203 |
209,701 |
395,204 |
50°C |
290,106 |
170,085 |
628,649 |
160,424 |
678,752 |
236,134 |
398,847 |
55°C |
293,143 |
183,900 |
640,931 |
170,718 |
728,989 |
245,881 |
399,398 |
60°C |
294,373 |
188,828 |
642,991 |
176,284 |
744,024 |
246,189 |
399,419 |
65°C |
294,515 |
192,778 |
645,023 |
178,117 |
747,483 |
257,387 |
399,419 |
70°C |
294,515 |
195,843 |
645,503 |
178,942 |
751,827 |
257,475 |
399,419 |
75°C |
294,515 |
197,868 |
645,503 |
179,580 |
754,120 |
258,921 |
399,419 |
80°C |
294,515 |
198,036 |
645,503 |
179,580 |
755,251 |
258,972 |
399,419 |
85°C |
294,515 |
198,432 |
645,503 |
179,580 |
755,251 |
262,795 |
399,419 |
90°C |
294,515 |
202,925 |
645,503 |
179,580 |
755,251 |
269,874 |
399,419 |
November average – Lower cost retrofit scenario (reduced radiators)
Number of dwellings suitable at each flow temperature, by archetype | |||||||
Pre-1919 flat |
Pre-1919 house |
1919-2002 flat |
1919-1949 house |
1950-1983 house |
1984-2002 house |
Post-2002 | |
30°C |
– |
– |
556 |
– |
– |
– |
– |
35°C |
– |
– |
17,237 |
– |
664 |
6,127 |
1,007 |
40°C |
2,370 |
– |
103,816 |
4,167 |
13,449 |
12,299 |
49,933 |
45°C |
40,879 |
14,815 |
298,689 |
43,596 |
177,161 |
73,365 |
195,602 |
50°C |
173,946 |
63,963 |
484,267 |
105,530 |
470,477 |
190,966 |
329,467 |
55°C |
242,251 |
118,811 |
575,934 |
136,028 |
617,415 |
213,816 |
378,780 |
60°C |
282,120 |
155,995 |
611,550 |
157,415 |
714,411 |
241,242 |
393,466 |
65°C |
283,309 |
180,168 |
617,706 |
169,398 |
724,262 |
247,343 |
399,419 |
70°C |
294,515 |
186,097 |
639,442 |
173,231 |
731,429 |
247,343 |
399,419 |
75°C |
294,515 |
187,396 |
645,503 |
177,378 |
739,587 |
247,343 |
399,419 |
80°C |
294,515 |
188,201 |
645,503 |
177,651 |
745,384 |
247,343 |
399,419 |
85°C |
294,515 |
189,582 |
645,503 |
179,580 |
750,957 |
247,389 |
399,419 |
90°C |
294,515 |
202,925 |
645,503 |
179,580 |
755,251 |
269,874 |
399,419 |
November average – Higher cost retrofit scenario (reduced radiators)
Number of dwellings suitable at each flow temperature, by archetype | |||||||
Pre-1919 flat |
Pre-1919 house |
1919-2002 flat |
1919-1949 house |
1950-1983 house |
1984-2002 house |
Post-2002 | |
30°C |
– |
– |
384 |
– |
– |
– |
– |
35°C |
– |
– |
19,069 |
87 |
5,312 |
6,143 |
971 |
40°C |
18,216 |
14,694 |
151,171 |
12,497 |
58,928 |
21,050 |
56,091 |
45°C |
81,548 |
65,841 |
388,607 |
64,348 |
268,811 |
106,725 |
191,927 |
50°C |
208,301 |
118,870 |
532,422 |
117,153 |
546,140 |
205,234 |
367,444 |
55°C |
268,302 |
158,015 |
593,498 |
146,045 |
671,635 |
228,642 |
385,410 |
60°C |
284,142 |
173,340 |
612,043 |
163,855 |
719,503 |
242,036 |
399,419 |
65°C |
284,284 |
185,993 |
639,265 |
172,880 |
728,556 |
247,343 |
399,419 |
70°C |
294,515 |
191,020 |
645,503 |
175,165 |
736,537 |
247,431 |
399,419 |
75°C |
294,515 |
193,045 |
645,503 |
177,637 |
746,875 |
248,877 |
399,419 |
80°C |
294,515 |
193,213 |
645,503 |
179,580 |
751,960 |
248,928 |
399,419 |
85°C |
294,515 |
195,337 |
645,503 |
179,580 |
755,251 |
249,955 |
399,419 |
90°C |
294,515 |
202,925 |
645,503 |
179,580 |
755,251 |
269,874 |
399,419 |
Detailed results – fuel bill modelling
Winter average – suitability now
Savings, by archetype (£million) and by dwelling (£) |
Reduction to 55°C |
Reduction to 50°C | ||||||
Archetype (£m) |
Dwelling (£) |
Archetype (£m) |
Dwelling (£) | |||||
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price | |
Pre-1919 flat |
28.40 |
64.99 |
96.41 |
220.68 |
29.79 |
68.19 |
101.16 |
231.55 |
Pre-1919 house |
6.14 |
14.07 |
30.28 |
69.31 |
6.57 |
15.04 |
32.38 |
74.12 |
1919-2002 flat |
58.97 |
134.97 |
91.35 |
209.09 |
76.92 |
176.07 |
119.17 |
272.76 |
1919-1949 house |
11.40 |
26.10 |
63.49 |
145.33 |
13.07 |
29.91 |
72.76 |
166.53 |
1950-1983 house |
45.28 |
103.63 |
59.95 |
137.22 |
52.06 |
119.16 |
68.93 |
157.78 |
1984-2002 house |
24.95 |
57.11 |
92.46 |
211.63 |
29.26 |
66.98 |
108.43 |
248.19 |
Post-2002 |
21.44 |
49.07 |
53.68 |
122.87 |
26.94 |
61.66 |
67.45 |
154.38 |
Total/Average (archetype/dwelling) |
196.58 |
449.95 |
71.56 |
163.79 |
234.62 |
537.02 |
85.41 |
195.49 |
Winter average – Lower cost retrofit scenario
Savings, by archetype (£million) and by dwelling (£) |
Reduction to 55°C |
Reduction to 50°C | ||||||
Archetype (£m) |
Dwelling (£) |
Archetype (£m) |
Dwelling (£) | |||||
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price | |
Pre-1919 flat |
36.34 |
123.38 |
83.17 |
282.39 |
49.42 |
113.11 |
167.79 |
384.05 |
Pre-1919 house |
8.29 |
40.83 |
18.96 |
93.45 |
9.20 |
21.06 |
45.34 |
103.77 |
1919-2002 flat |
68.95 |
106.82 |
157.82 |
244.49 |
99.40 |
227.51 |
153.98 |
352.45 |
1919-1949 house |
13.60 |
75.73 |
31.13 |
173.34 |
17.85 |
40.86 |
99.40 |
227.51 |
1950-1983 house |
55.31 |
73.24 |
126.60 |
167.63 |
74.15 |
169.73 |
98.18 |
224.73 |
1984-2002 house |
27.12 |
100.51 |
62.08 |
230.05 |
35.85 |
82.06 |
132.84 |
304.06 |
Post-2002 |
23.80 |
59.58 |
54.47 |
136.38 |
32.39 |
74.13 |
81.09 |
185.61 |
Total/Average (archetype/dwelling) |
233.41 |
580.09 |
98.26 |
194.48 |
318.26 |
728.45 |
115.85 |
265.17 |
Winter average – Higher cost retrofit scenario
Savings, by archetype (£million) and by dwelling (£) |
Reduction to 55°C |
Reduction to 50°C | ||||||
Archetype (£m) |
Dwelling (£) |
Archetype (£m) |
Dwelling (£) | |||||
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price | |
Pre-1919 flat |
38.19 |
129.66 |
87.40 |
296.77 |
55.19 |
126.33 |
187.40 |
428.93 |
Pre-1919 house |
12.00 |
59.14 |
27.47 |
135.37 |
16.31 |
37.33 |
80.36 |
183.94 |
1919-2002 flat |
68.88 |
106.71 |
157.66 |
244.24 |
99.75 |
228.31 |
154.53 |
353.69 |
1919-1949 house |
15.21 |
84.71 |
34.82 |
193.90 |
21.48 |
49.16 |
119.59 |
273.73 |
1950-1983 house |
56.94 |
75.40 |
130.33 |
172.57 |
80.16 |
183.47 |
106.13 |
242.93 |
1984-2002 house |
29.15 |
108.00 |
66.71 |
247.20 |
41.78 |
95.62 |
154.80 |
354.32 |
Post-2002 |
24.23 |
60.67 |
55.47 |
138.88 |
35.80 |
81.95 |
89.64 |
205.18 |
Total/Average (archetype/dwelling) |
244.60 |
624.29 |
101.17 |
203.81 |
350.46 |
802.16 |
127.58 |
292.01 |
Winter peak – suitability now
Savings, by archetype (£million) and by dwelling (£) |
Reduction to 55°C |
Reduction to 50°C | ||||||
Archetype (£m) |
Dwelling (£) |
Archetype (£m) |
Dwelling (£) | |||||
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price | |
Pre-1919 flat |
9.17 |
20.98 |
31.12 |
71.23 |
9.17 |
20.98 |
31.12 |
71.23 |
Pre-1919 house |
1.47 |
3.36 |
7.23 |
16.55 |
1.47 |
3.36 |
7.23 |
16.55 |
1919-2002 flat |
35.59 |
81.46 |
55.13 |
126.19 |
40.09 |
91.75 |
62.10 |
142.14 |
1919-1949 house |
4.85 |
11.11 |
27.03 |
61.87 |
4.97 |
11.38 |
27.69 |
63.37 |
1950-1983 house |
18.92 |
43.30 |
25.05 |
57.34 |
19.58 |
44.81 |
25.92 |
59.33 |
1984-2002 house |
12.07 |
27.62 |
44.72 |
102.35 |
12.42 |
28.43 |
46.03 |
105.35 |
Post-2002 |
12.42 |
28.42 |
31.08 |
71.15 |
13.53 |
30.96 |
33.87 |
77.52 |
Total/Average (archetype/dwelling) |
94.49 |
216.25 |
34.39 |
78.82 |
101.23 |
231.67 |
36.85 |
84.33 |
Winter peak – Lower cost retrofit scenario
Savings, by archetype (£million) and by dwelling (£) |
Reduction to 55°C |
Reduction to 50°C | ||||||
Archetype (£m) |
Dwelling (£) |
Archetype (£m) |
Dwelling (£) | |||||
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price | |
Pre-1919 flat |
26.40 |
60.42 |
89.63 |
205.14 |
31.96 |
73.16 |
108.52 |
248.40 |
Pre-1919 house |
3.03 |
6.94 |
14.95 |
34.21 |
3.09 |
7.08 |
15.23 |
34.87 |
1919-2002 flat |
62.18 |
142.32 |
96.32 |
220.48 |
82.75 |
189.40 |
128.19 |
293.41 |
1919-1949 house |
9.13 |
20.89 |
50.83 |
116.35 |
10.78 |
24.68 |
60.04 |
137.43 |
1950-1983 house |
40.79 |
93.35 |
54.00 |
123.61 |
49.81 |
114.01 |
65.95 |
150.95 |
1984-2002 house |
20.38 |
46.65 |
75.53 |
172.87 |
24.57 |
56.25 |
91.06 |
208.42 |
Post-2002 |
19.13 |
43.80 |
47.91 |
109.65 |
23.77 |
54.41 |
59.51 |
136.21 |
Total/Average (archetype/dwelling) |
181.04 |
414.37 |
65.90 |
150.84 |
226.73 |
518.99 |
82.53 |
188.91 |
Winter Peak – Higher cost retrofit scenario
Savings, by archetype (£million) and by dwelling (£) |
Reduction to 55°C |
Reduction to 50°C | ||||||
Archetype |
Dwelling |
Archetype |
Dwelling | |||||
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price | |
Pre-1919 flat |
34.58 |
79.16 |
117.43 |
268.78 |
44.00 |
100.70 |
149.38 |
341.92 |
Pre-1919 house |
9.19 |
21.03 |
45.27 |
103.62 |
10.64 |
24.36 |
52.44 |
120.03 |
1919-2002 flat |
64.40 |
147.40 |
99.76 |
228.35 |
89.73 |
205.37 |
139.00 |
318.16 |
1919-1949 house |
12.95 |
29.63 |
72.09 |
165.00 |
16.78 |
38.40 |
93.42 |
213.82 |
1950-1983 house |
47.85 |
109.52 |
63.35 |
145.01 |
61.24 |
140.18 |
81.09 |
185.61 |
1984-2002 house |
26.01 |
59.54 |
96.39 |
220.63 |
34.40 |
78.73 |
127.46 |
291.74 |
Post-2002 |
23.92 |
54.75 |
59.89 |
137.08 |
34.14 |
78.15 |
85.48 |
195.65 |
Total/Average (archetype/dwelling) |
218.9 |
501.03 |
79.68 |
182.39 |
290.93 |
665.89 |
105.90 |
242.40 |
Winter peak – Lower cost retrofit scenario (reduced radiators)
Savings, by archetype (£million) and by dwelling (£) |
Reduction to 55°C |
Reduction to 50°C | ||||||
Archetype (£m) |
Dwelling (£) |
Archetype (£m) |
Dwelling (£) | |||||
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price | |
Pre-1919 flat |
10.91 |
24.98 |
37.06 |
84.83 |
11.06 |
25.32 |
37.56 |
85.98 |
Pre-1919 house |
2.36 |
5.40 |
11.63 |
26.63 |
2.36 |
5.40 |
11.63 |
26.63 |
1919-2002 flat |
38.55 |
88.23 |
59.71 |
136.68 |
43.97 |
100.65 |
68.12 |
155.92 |
1919-1949 house |
6.29 |
14.39 |
35.01 |
80.14 |
6.46 |
14.78 |
35.97 |
82.33 |
1950-1983 house |
23.11 |
52.89 |
30.60 |
70.03 |
24.08 |
55.12 |
31.88 |
72.98 |
1984-2002 house |
14.72 |
33.70 |
54.56 |
124.88 |
15.32 |
35.07 |
56.77 |
129.93 |
Post-2002 |
14.97 |
34.27 |
37.49 |
85.81 |
16.43 |
37.61 |
41.13 |
94.15 |
Total/Average (archetype/dwelling) |
110.91 |
253.87 |
40.38 |
92.41 |
119.69 |
273.95 |
43.57 |
99.72 |
Winter peak – Higher cost retrofit scenario (reduced radiators)
Savings, by archetype (£million) and by dwelling (£) |
Reduction to 55°C |
Reduction to 50°C | ||||||
Archetype (£m) |
Dwelling (£) |
Archetype (£m) |
Dwelling (£) | |||||
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price | |
Pre-1919 flat |
15.91 |
36.43 |
54.04 |
123.68 |
16.95 |
38.80 |
57.56 |
131.74 |
Pre-1919 house |
5.74 |
13.13 |
28.27 |
64.72 |
6.30 |
14.41 |
31.03 |
71.03 |
1919-2002 flat |
44.71 |
102.34 |
69.26 |
158.54 |
52.73 |
120.69 |
81.68 |
186.96 |
1919-1949 house |
7.63 |
17.46 |
42.47 |
97.20 |
8.21 |
18.78 |
45.69 |
104.59 |
1950-1983 house |
30.66 |
70.18 |
40.60 |
92.93 |
33.16 |
75.91 |
43.91 |
100.51 |
1984-2002 house |
17.59 |
40.25 |
65.16 |
149.15 |
18.91 |
43.29 |
70.08 |
160.40 |
Post-2002 |
15.52 |
35.53 |
38.86 |
88.95 |
17.17 |
39.29 |
42.98 |
98.37 |
Total/Average (archetype/dwelling) |
137.76 |
315.31 |
50.15 |
114.78 |
153.42 |
351.17 |
55.85 |
127.83 |
20-year peak – suitability now (all 20-year peak scenarios)
Savings, by archetype (£million) and by dwelling (£) |
Reduction to 55°C |
Reduction to 50°C | ||||||
Archetype (£m) |
Dwelling (£) |
Archetype (£m) |
Dwelling (£) | |||||
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price | |
Pre-1919 flat |
2.84 |
6.49 |
9.63 |
22.04 |
2.84 |
6.49 |
9.63 |
22.04 |
Pre-1919 house |
4.42 |
10.11 |
21.76 |
49.81 |
4.42 |
10.11 |
21.76 |
49.81 |
1919-2002 flat |
26.03 |
59.57 |
40.32 |
92.29 |
28.86 |
66.06 |
44.71 |
102.34 |
1919-1949 house |
2.82 |
6.45 |
15.69 |
35.90 |
2.82 |
6.45 |
15.69 |
35.90 |
1950-1983 house |
10.51 |
24.05 |
13.91 |
31.84 |
10.70 |
24.50 |
14.17 |
32.43 |
1984-2002 house |
6.51 |
14.91 |
24.13 |
55.24 |
6.87 |
15.72 |
25.45 |
58.24 |
Post-2002 |
8.62 |
19.72 |
21.58 |
49.38 |
8.86 |
20.29 |
22.19 |
50.79 |
Total/Average (archetype/dwelling) |
61.73 |
141.30 |
22.47 |
51.44 |
65.36 |
149.61 |
23.79 |
54.46 |
20-year peak – Lower cost retrofit scenario
Savings, by archetype (£million) and by dwelling (£) |
Reduction to 55°C |
Reduction to 50°C | ||||||
Archetype (£m) |
Dwelling (£) |
Archetype (£m) |
Dwelling (£) | |||||
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price | |
Pre-1919 flat |
21.45 |
49.09 |
72.83 |
166.69 |
23.06 |
52.78 |
78.30 |
179.22 |
Pre-1919 house |
1.59 |
3.63 |
7.82 |
17.90 |
1.65 |
3.77 |
8.11 |
18.56 |
1919-2002 flat |
56.76 |
129.92 |
87.94 |
201.28 |
73.49 |
168.21 |
113.85 |
260.58 |
1919-1949 house |
6.88 |
15.75 |
38.32 |
87.71 |
7.89 |
18.05 |
43.91 |
100.50 |
1950-1983 house |
33.02 |
75.58 |
43.72 |
100.07 |
38.02 |
87.03 |
50.35 |
115.24 |
1984-2002 house |
15.24 |
34.87 |
56.45 |
129.22 |
17.19 |
39.34 |
63.68 |
145.76 |
Post-2002 |
15.87 |
36.32 |
39.73 |
90.93 |
19.48 |
44.59 |
48.77 |
111.64 |
Total/Average (archetype/dwelling) |
150.80 |
345.17 |
54.90 |
125.65 |
180.77 |
413.76 |
65.81 |
150.62 |
20-year peak – Higher cost retrofit scenario
Savings, by archetype (£million) and by dwelling (£) |
Reduction to 55°C |
Reduction to 50°C | ||||||
Archetype (£m) |
Dwelling (£) |
Archetype (£m) |
Dwelling (£) | |||||
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price | |
Pre-1919 flat |
30.40 |
69.59 |
103.23 |
236.28 |
36.12 |
82.67 |
122.64 |
280.70 |
Pre-1919 house |
7.16 |
16.39 |
35.29 |
80.78 |
7.98 |
18.26 |
39.31 |
89.98 |
1919-2002 flat |
60.70 |
138.94 |
94.04 |
215.24 |
80.47 |
184.19 |
124.66 |
285.34 |
1919-1949 house |
11.38 |
26.04 |
63.35 |
145.00 |
14.06 |
32.19 |
78.31 |
179.23 |
1950-1983 house |
41.44 |
94.85 |
54.87 |
125.59 |
50.47 |
115.52 |
66.82 |
152.95 |
1984-2002 house |
23.62 |
54.06 |
87.52 |
200.31 |
30.63 |
70.10 |
113.49 |
259.76 |
Post-2002 |
23.48 |
53.75 |
58.79 |
134.57 |
31.47 |
72.04 |
78.80 |
180.36 |
Total/Average (archetype/dwelling) |
198.18 |
453.62 |
72.14 |
165.13 |
251.20 |
574.96 |
91.44 |
209.30 |
20-year peak – Lower cost retrofit scenario (reduced radiators)
Savings, by archetype (£million) and by dwelling (£) |
Reduction to 55°C |
Reduction to 50°C | ||||||
Archetype (£m) |
Dwelling (£) |
Archetype (£m) |
Dwelling (£) | |||||
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price | |
Pre-1919 flat |
5.23 |
11.96 |
17.75 |
40.62 |
5.23 |
11.96 |
17.75 |
40.62 |
Pre-1919 house |
1.16 |
2.65 |
5.71 |
13.07 |
1.16 |
2.65 |
5.71 |
13.07 |
1919-2002 flat |
28.86 |
66.06 |
44.71 |
102.34 |
32.30 |
73.93 |
50.04 |
114.53 |
1919-1949 house |
3.83 |
8.77 |
21.34 |
48.85 |
3.86 |
8.83 |
21.48 |
49.17 |
1950-1983 house |
13.88 |
31.76 |
18.37 |
42.05 |
14.17 |
32.44 |
18.76 |
42.95 |
1984-2002 house |
8.46 |
19.37 |
31.36 |
71.79 |
8.82 |
20.19 |
32.68 |
74.80 |
Post-2002 |
9.97 |
22.81 |
24.95 |
57.11 |
10.56 |
24.16 |
26.43 |
60.49 |
Total/Average (archetype/dwelling) |
71.39 |
163.39 |
25.99 |
59.48 |
76.09 |
174.16 |
27.70 |
63.40 |
20-year peak – Higher cost retrofit scenario (reduced radiators)
Savings, by archetype (£million) and by dwelling (£) |
Reduction to 55°C |
Reduction to 50°C | ||||||
Archetype (£m) |
Dwelling (£) |
Archetype (£m) |
Dwelling (£) | |||||
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price | |
Pre-1919 flat |
9.85 |
22.55 |
33.45 |
76.56 |
10.09 |
23.10 |
34.27 |
78.44 |
Pre-1919 house |
3.90 |
8.92 |
19.20 |
43.94 |
4.21 |
9.63 |
20.74 |
47.47 |
1919-2002 flat |
34.57 |
79.12 |
53.55 |
122.56 |
38.98 |
89.23 |
60.39 |
138.23 |
1919-1949 house |
5.07 |
11.61 |
28.24 |
64.63 |
5.26 |
12.03 |
29.28 |
67.02 |
1950-1983 house |
20.48 |
46.88 |
27.12 |
62.08 |
21.60 |
49.44 |
28.60 |
65.46 |
1984-2002 house |
12.16 |
27.84 |
45.07 |
103.17 |
12.84 |
29.39 |
47.58 |
108.90 |
Post-2002 |
11.36 |
26.01 |
28.45 |
65.12 |
12.27 |
28.10 |
30.73 |
70.34 |
Total/Average (archetype/dwelling) |
97.39 |
222.92 |
35.45 |
81.15 |
105.26 |
240.92 |
38.32 |
87.70 |
November average – suitability now
Savings, by archetype (£million) and by dwelling (£) |
Reduction to 55°C |
Reduction to 50°C | ||||||
Archetype (£m) |
Dwelling (£) |
Archetype (£m) |
Dwelling (£) | |||||
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price | |
Pre-1919 flat |
34.45 |
78.85 |
116.97 |
267.74 |
43.87 |
100.41 |
148.95 |
340.94 |
Pre-1919 house |
8.94 |
20.47 |
44.08 |
100.89 |
10.06 |
23.02 |
49.55 |
113.42 |
1919-2002 flat |
65.06 |
148.91 |
100.79 |
230.69 |
89.41 |
204.64 |
138.51 |
317.03 |
1919-1949 house |
13.34 |
30.53 |
74.28 |
170.02 |
17.12 |
39.19 |
95.34 |
218.21 |
1950-1983 house |
53.36 |
122.13 |
70.65 |
161.70 |
68.90 |
157.70 |
91.23 |
208.81 |
1984-2002 house |
27.59 |
63.16 |
102.25 |
234.04 |
38.16 |
87.35 |
141.41 |
323.67 |
Post-2002 |
23.65 |
54.14 |
59.22 |
135.54 |
31.12 |
71.22 |
77.91 |
178.32 |
Total/Average (archetype/dwelling) |
226.40 |
518.20 |
82.41 |
188.64 |
298.63 |
683.54 |
108.71 |
248.82 |
November average – Lower cost retrofit scenario
Savings, by archetype (£million) and by dwelling (£) |
Reduction to 55°C |
Reduction to 50°C | ||||||
Archetype (£m) |
Dwelling (£) |
Archetype (£m) |
Dwelling (£) | |||||
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price | |
Pre-1919 flat |
37.70 |
86.30 |
128.02 |
293.01 |
53.99 |
123.57 |
183.32 |
419.59 |
Pre-1919 house |
10.61 |
24.29 |
52.30 |
119.70 |
13.07 |
29.91 |
64.39 |
147.38 |
1919-2002 flat |
69.46 |
159.00 |
107.61 |
246.31 |
101.66 |
232.70 |
157.49 |
360.49 |
1919-1949 house |
14.88 |
34.05 |
82.84 |
189.60 |
20.58 |
47.12 |
114.63 |
262.37 |
1950-1983 house |
58.07 |
132.92 |
76.89 |
176.00 |
81.63 |
186.84 |
108.08 |
247.39 |
1984-2002 house |
28.76 |
65.82 |
106.55 |
243.89 |
40.87 |
93.55 |
151.45 |
346.64 |
Post-2002 |
24.10 |
55.16 |
60.34 |
138.11 |
35.31 |
80.83 |
88.41 |
202.36 |
Total/Average (archetype/dwelling) |
243.58 |
557.54 |
88.67 |
202.96 |
347.12 |
794.51 |
126.36 |
289.22 |
November average – Higher cost retrofit scenario
Savings, by archetype (£million) and by dwelling (£) |
Reduction to 55°C |
Reduction to 50°C | ||||||
Archetype (£m) |
Dwelling (£) |
Archetype (£m) |
Dwelling (£) | |||||
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price |
Lower fuel price |
Higher fuel price | |
Pre-1919 flat |
38.33 |
87.72 |
130.13 |
297.86 |
56.50 |
129.33 |
191.85 |
439.12 |
Pre-1919 house |
12.46 |
28.52 |
61.40 |
140.55 |
17.84 |
40.84 |
87.92 |
201.24 |
1919-2002 flat |
69.46 |
158.99 |
107.61 |
246.30 |
102.09 |
233.67 |
158.16 |
362.00 |
1919-1949 house |
15.68 |
35.89 |
87.32 |
199.86 |
22.58 |
51.68 |
125.73 |
287.78 |
1950-1983 house |
58.72 |
134.40 |
77.75 |
177.96 |
84.57 |
193.57 |
111.97 |
256.30 |
1984-2002 house |
30.12 |
68.95 |
111.62 |
255.50 |
43.76 |
100.16 |
162.14 |
371.13 |
Post-2002 |
24.25 |
55.50 |
60.70 |
138.94 |
35.88 |
82.13 |
89.84 |
205.63 |
Total/Average (archetype/dwelling) |
249.02 |
569.98 |
90.65 |
207.49 |
363.22 |
831.38 |
132.22 |
302.64 |
Detailed results – emissions modelling
Winter average – suitability now
Savings, by archetype (MtCO2/yr) and by dwelling (tCO2/yr) |
Reduction to 55°C |
Reduction to 50°C | ||
Archetype |
Dwelling |
Archetype |
Dwelling | |
1.16 |
3.94 |
1.22 |
4.14 | |
Pre-1919 house |
0.25 |
1.24 |
0.27 |
1.32 |
1919-2002 flat |
2.41 |
3.74 |
3.15 |
4.87 |
1919-1949 house |
0.47 |
2.60 |
0.53 |
2.97 |
1950-1983 house |
1.85 |
2.45 |
2.13 |
2.82 |
1984-2002 house |
1.02 |
3.78 |
1.20 |
4.43 |
Post-2002 |
0.88 |
2.19 |
1.10 |
2.76 |
Total/Average (archetype/dwelling) |
8.04 |
2.93 |
9.59 |
3.49 |
Winter average – Lower cost retrofit scenario
Savings, by archetype (MtCO2/yr) and by dwelling (tCO2/yr) |
Reduction to 55°C |
Reduction to 50°C | ||
Archetype |
Dwelling |
Archetype |
Dwelling | |
Pre-1919 flat |
1.49 |
5.04 |
2.02 |
6.86 |
Pre-1919 house |
0.34 |
1.67 |
0.38 |
1.85 |
1919-2002 flat |
2.82 |
4.37 |
4.06 |
6.30 |
1919-1949 house |
0.56 |
3.10 |
0.73 |
4.06 |
1950-1983 house |
2.26 |
2.99 |
3.03 |
4.01 |
1984-2002 house |
1.11 |
4.11 |
1.47 |
5.43 |
Post-2002 |
0.97 |
2.44 |
1.32 |
3.32 |
Total/Average (archetype/dwelling) |
9.54 |
3.47 |
13.01 |
4.74 |
Winter average – Higher cost retrofit scenario
Savings, by archetype (MtCO2/yr) and by dwelling (tCO2/yr) |
Reduction to 55°C |
Reduction to 50°C | ||
Archetype |
Dwelling |
Archetype |
Dwelling | |
Pre-1919 flat |
1.56 |
5.30 |
2.26 |
7.66 |
Pre-1919 house |
0.49 |
2.42 |
0.67 |
3.29 |
1919-2002 flat |
2.82 |
4.36 |
4.08 |
6.32 |
1919-1949 house |
0.62 |
3.46 |
0.88 |
4.89 |
1950-1983 house |
2.33 |
3.08 |
3.28 |
4.34 |
1984-2002 house |
1.19 |
4.42 |
1.71 |
6.33 |
Post-2002 |
0.99 |
2.48 |
1.46 |
3.67 |
Total/Average (archetype/dwelling) |
10.00 |
3.64 |
14.33 |
5.22 |
Winter peak – suitability now
Savings, by archetype (MtCO2/yr) and by dwelling (tCO2/yr) |
Reduction to 55°C |
Reduction to 50°C | ||
Archetype |
Dwelling |
Archetype |
Dwelling | |
Pre-1919 flat |
0.37 |
1.27 |
0.37 |
1.27 |
Pre-1919 house |
0.06 |
0.30 |
0.06 |
0.30 |
1919-2002 flat |
1.46 |
2.25 |
1.64 |
2.54 |
1919-1949 house |
0.20 |
1.11 |
0.20 |
1.13 |
1950-1983 house |
0.77 |
1.02 |
0.80 |
1.06 |
1984-2002 house |
0.49 |
1.83 |
0.51 |
1.88 |
Post-2002 |
0.51 |
1.27 |
0.55 |
1.38 |
Total/Average (archetype/dwelling) |
3.86 |
1.41 |
4.14 |
1.51 |
Winter peak – Lower cost retrofit scenario
Savings, by archetype (MtCO2/yr) and by dwelling (tCO2/yr) |
Reduction to 55°C |
Reduction to 50°C | ||
Archetype |
Dwelling |
Archetype |
Dwelling | |
Pre-1919 flat |
1.08 |
3.66 |
1.31 |
4.44 |
Pre-1919 house |
0.12 |
0.61 |
0.13 |
0.62 |
1919-2002 flat |
2.54 |
3.94 |
3.38 |
5.24 |
1919-1949 house |
0.37 |
2.08 |
0.44 |
2.46 |
1950-1983 house |
1.67 |
2.21 |
2.04 |
2.70 |
1984-2002 house |
0.83 |
3.09 |
1.00 |
3.72 |
Post-2002 |
0.78 |
1.96 |
0.97 |
2.43 |
Total/Average (archetype/dwelling) |
7.40 |
2.69 |
9.27 |
3.37 |
Winter peak – Higher cost retrofit scenario
Savings, by archetype (MtCO2/yr) and by dwelling (tCO2/yr) |
Reduction to 55°C |
Reduction to 50°C | ||
Archetype |
Dwelling |
Archetype |
Dwelling | |
Pre-1919 flat |
1.41 |
4.80 |
1.80 |
6.11 |
Pre-1919 house |
0.38 |
1.85 |
0.38 |
2.14 |
1919-2002 flat |
2.63 |
4.08 |
3.67 |
5.68 |
1919-1949 house |
0.53 |
2.95 |
0.69 |
3.82 |
1950-1983 house |
1.96 |
2.59 |
2.50 |
3.32 |
1984-2002 house |
1.06 |
3.94 |
1.41 |
5.21 |
Post-2002 |
0.98 |
2.45 |
1.40 |
3.50 |
Total/Average (archetype/dwelling) |
8.95 |
3.26 |
11.85 |
4.33 |
Winter peak – Lower cost retrofit scenario (reduced radiators)
Savings, by archetype (MtCO2/yr) and by dwelling (tCO2/yr) |
Reduction to 55°C |
Reduction to 50°C | ||
Archetype |
Dwelling |
Archetype |
Dwelling | |
Pre-1919 flat |
0.45 |
1.52 |
0.45 |
1.54 |
Pre-1919 house |
0.10 |
0.48 |
0.10 |
0.48 |
1919-2002 flat |
1.58 |
2.44 |
1.80 |
2.79 |
1919-1949 house |
0.26 |
1.43 |
0.26 |
1.47 |
1950-1983 house |
0.94 |
1.25 |
0.98 |
1.30 |
1984-2002 house |
0.60 |
2.23 |
0.63 |
2.32 |
Post-2002 |
0.61 |
1.53 |
0.67 |
1.68 |
Total/Average (archetype/dwelling) |
4.54 |
1.65 |
4.89 |
1.78 |
Winter peak – Higher cost retrofit scenario (reduced radiators)
Savings, by archetype (MtCO2/yr) and by dwelling (tCO2/yr) |
Reduction to 55°C |
Reduction to 50°C | ||
Archetype |
Dwelling |
Archetype |
Dwelling | |
Pre-1919 flat |
0.65 |
2.21 |
0.69 |
2.35 |
Pre-1919 house |
0.23 |
1.16 |
0.26 |
1.27 |
1919-2002 flat |
1.83 |
2.83 |
2.16 |
3.34 |
1919-1949 house |
0.31 |
1.74 |
0.34 |
1.87 |
1950-1983 house |
1.25 |
1.66 |
1.36 |
1.80 |
1984-2002 house |
0.72 |
2.66 |
0.77 |
2.87 |
Post-2002 |
0.63 |
1.59 |
0.70 |
1.76 |
Total/Average (archetype/dwelling) |
5.63 |
2.05 |
6.27 |
2.28 |
20-year peak – suitability now (all 20-year peak scenarios)
Savings, by archetype (MtCO2/yr) and by dwelling (tCO2/yr) |
Reduction to 55°C |
Reduction to 50°C | ||
Archetype |
Dwelling |
Archetype |
Dwelling | |
Pre-1919 flat |
0.12 |
0.39 |
0.12 |
0.39 |
Pre-1919 house |
0.18 |
0.89 |
0.18 |
0.89 |
1919-2002 flat |
1.06 |
1.65 |
1.18 |
1.83 |
1919-1949 house |
0.12 |
0.64 |
0.12 |
0.64 |
1950-1983 house |
0.43 |
0.57 |
0.44 |
0.58 |
1984-2002 house |
0.27 |
0.99 |
0.28 |
1.04 |
Post-2002 |
0.35 |
0.88 |
0.36 |
0.91 |
Total/Average (archetype/dwelling) |
2.52 |
0.92 |
2.67 |
0.97 |
20-year peak – Lower cost retrofit scenario
Savings, by archetype (MtCO2/yr) and by dwelling (tCO2/yr) |
Reduction to 55°C |
Reduction to 50°C | ||
Archetype |
Dwelling |
Archetype |
Dwelling | |
Pre-1919 flat |
0.88 |
2.98 |
0.94 |
3.20 |
Pre-1919 house |
0.06 |
0.32 |
0.07 |
0.33 |
1919-2002 flat |
2.32 |
3.60 |
3.00 |
4.66 |
1919-1949 house |
0.28 |
1.57 |
0.32 |
1.80 |
1950-1983 house |
1.35 |
1.79 |
1.55 |
2.06 |
1984-2002 house |
0.62 |
2.31 |
0.70 |
2.60 |
Post-2002 |
0.65 |
1.62 |
0.80 |
1.99 |
Total/Average (archetype/dwelling) |
6.17 |
2.24 |
7.39 |
2.69 |
20-year peak – Higher cost retrofit scenario
Savings, by archetype (MtCO2/yr) and by dwelling (tCO2/yr) |
Reduction to 55°C |
Reduction to 50°C | ||
Archetype |
Dwelling |
Archetype |
Dwelling | |
Pre-1919 flat |
1.24 |
4.22 |
1.48 |
5.01 |
Pre-1919 house |
0.29 |
1.44 |
0.33 |
1.61 |
1919-2002 flat |
2.48 |
3.85 |
3.29 |
5.10 |
1919-1949 house |
0.47 |
2.59 |
0.57 |
3.20 |
1950-1983 house |
1.69 |
2.24 |
2.06 |
2.73 |
1984-2002 house |
0.97 |
3.58 |
1.25 |
4.64 |
Post-2002 |
0.96 |
2.40 |
1.29 |
3.22 |
Total/Average (archetype/dwelling) |
8.10 |
2.95 |
10.27 |
3.74 |
20-year peak – Lower cost retrofit scenario (reduced radiators)
Savings, by archetype (MtCO2/yr) and by dwelling (tCO2/yr) |
Reduction to 55°C |
Reduction to 50°C | ||
Archetype |
Dwelling |
Archetype |
Dwelling | |
Pre-1919 flat |
0.21 |
0.73 |
0.21 |
0.73 |
Pre-1919 house |
0.05 |
0.23 |
0.05 |
0.23 |
1919-2002 flat |
1.18 |
1.83 |
1.32 |
2.05 |
1919-1949 house |
0.16 |
0.87 |
0.16 |
0.88 |
1950-1983 house |
0.57 |
0.75 |
0.58 |
0.77 |
1984-2002 house |
0.35 |
1.28 |
0.36 |
1.34 |
Post-2002 |
0.41 |
1.02 |
0.43 |
1.08 |
Total/Average (archetype/dwelling) |
2.92 |
1.06 |
3.11 |
1.13 |
20-year peak – Higher cost retrofit scenario (reduced radiators)
Savings, by archetype (MtCO2/yr) and by dwelling (tCO2/yr) |
Reduction to 55°C |
Reduction to 50°C | ||
Archetype |
Dwelling |
Archetype |
Dwelling | |
Pre-1919 flat |
0.40 |
1.37 |
0.41 |
1.40 |
Pre-1919 house |
0.16 |
0.78 |
0.17 |
0.85 |
1919-2002 flat |
1.41 |
2.19 |
1.59 |
2.47 |
1919-1949 house |
0.21 |
1.15 |
0.21 |
1.20 |
1950-1983 house |
0.84 |
1.11 |
0.88 |
1.17 |
1984-2002 house |
0.50 |
1.84 |
0.53 |
1.95 |
Post-2002 |
0.46 |
1.16 |
0.50 |
1.26 |
Total/Average (archetype/dwelling) |
3.98 |
1.45 |
4.30 |
1.57 |
November average – suitability now
Savings, by archetype (MtCO2/yr) and by dwelling (tCO2/yr) |
Reduction to 55°C |
Reduction to 50°C | ||
Archetype |
Dwelling |
Archetype |
Dwelling | |
Pre-1919 flat |
1.41 |
4.78 |
1.79 |
6.09 |
Pre-1919 house |
0.37 |
1.80 |
0.41 |
2.03 |
1919-2002 flat |
2.66 |
4.12 |
3.66 |
5.66 |
1919-1949 house |
0.55 |
3.04 |
0.70 |
3.90 |
1950-1983 house |
2.18 |
2.89 |
2.82 |
3.73 |
1984-2002 house |
1.13 |
4.18 |
1.56 |
5.78 |
Post-2002 |
0.97 |
2.42 |
1.27 |
3.19 |
Total/Average (archetype/dwelling) |
9.26 |
3.37 |
12.21 |
4.45 |
November average – Lower cost retrofit scenario
Savings, by archetype (MtCO2/yr) and by dwelling (tCO2/yr) |
Reduction to 55°C |
Reduction to 50°C | ||
Archetype |
Dwelling |
Archetype |
Dwelling | |
Pre-1919 flat |
1.54 |
5.23 |
2.21 |
7.50 |
Pre-1919 house |
0.43 |
2.14 |
0.53 |
2.63 |
1919-2002 flat |
2.84 |
4.40 |
4.16 |
6.44 |
1919-1949 house |
0.61 |
3.39 |
0.84 |
4.69 |
1950-1983 house |
2.37 |
3.14 |
3.34 |
4.42 |
1984-2002 house |
1.18 |
4.36 |
1.67 |
6.19 |
Post-2002 |
0.99 |
2.47 |
1.44 |
3.62 |
Total/Average (archetype/dwelling) |
9.96 |
3.63 |
14.19 |
5.17 |
November average – Higher cost retrofit scenario
Savings, by archetype (MtCO2/yr) and by dwelling (tCO2/yr) |
Reduction to 55°C |
Reduction to 50°C | ||
Archetype |
Dwelling |
Archetype |
Dwelling | |
Pre-1919 flat |
1.57 |
5.32 |
2.31 |
7.84 |
Pre-1919 house |
0.51 |
2.51 |
0.73 |
3.59 |
1919-2002 flat |
2.84 |
4.40 |
4.17 |
6.47 |
1919-1949 house |
0.64 |
3.57 |
0.92 |
5.14 |
1950-1983 house |
2.40 |
3.18 |
3.46 |
4.58 |
1984-2002 house |
1.23 |
4.56 |
1.79 |
6.63 |
Post-2002 |
0.99 |
2.48 |
1.47 |
3.67 |
Total/Average (archetype/dwelling) |
10.18 |
3.71 |
14.85 |
5.41 |
References
British Gas (2022) What’s the ideal home temperature? Available at: https://www.britishgas.co.uk/the-source/no-place-like-home/whats-the-ideal-home-temperature.html#:~:text=And%20The%20World%20Health%20Organisation,the%20ideal%20temperature%20for%20sleeping
BEIS (2022) National Energy Efficiency Data-Framework (NEED). Available at: https://www.gov.uk/government/collections/national-energy-efficiency-data-need-framework
Climate Change Committee (CCC, 2022) Reducing energy demand in buildings in response to the energy price crisis. Climate Change Committee: London
Element Energy (2020a) Development of scenarios and trajectories to decarbonise residential homes, with a view to informing the UK’s long term targets: A study for the Committee on Climate Change
Element Energy (2020b) Technical Feasibility of Low Carbon Heating in Domestic Buildings. Scottish Government’s Directorate for Energy & Climate Change: Edinburgh
Element Energy (2021) Domestic heat distribution systems: evidence gathering, Department for Business, Energy & Industrial Strategy: London
Health and Safety Executive (HSE) Legionnaires’ disease: the control of legionella bacteria in water systems. London
Home Analytics Scotland (2022) Data services and tools – Home analytics. Available at: https://energysavingtrust.org.uk/service/home-analytics/
Microgeneration Certification Scheme (2019) Requirements for MCS contractors undertaking the supply, design, installation, set to work, commissioning and handover of microgeneration heat pump systems – Issue 5.0. Available at: https://mcscertified.com/wp-content/uploads/2019/08/MIS-3005.pdf
Nesta & Cambridge Architectural Research (2022) Money saving boiler challenge: supporting evidence. Nesta: London
Nesta & University of Salford (2022) Salford Energy House Boiler Flow Temperature Testing: Initial Report
Scottish Government (2021) Scottish House Condition Survey. Available at: https://www.gov.scot/collections/scottish-house-condition-survey/
Veissmann (2016) Control technology: Weather compensated controls. Viessmann: Telford
Watson, Lomas and Buswell (2019) Decarbonising domestic heating: What is the peak GB demand?. Energy Policy. 126. (pp. 533 – 544). Available at: https://doi.org/10.1016/j.enpol.2018.11.001
How to cite this publication:
Martin, M; Foster, S; Dias, J; Benjamin, S. (2023) Reductions in maximum flow temperatures in Scottish domestic heating, ClimateXChange. http://dx.doi.org/10.7488/era/3385
© The University of Edinburgh, 2025
Prepared by Element Energy (ERM Group) on behalf of ClimateXChange, The University of Edinburgh. All rights reserved.
While every effort is made to ensure the information in this report is accurate, no legal responsibility is accepted for any errors, omissions or misleading statements. The views expressed represent those of the author(s), and do not necessarily represent those of the host institutions or funders.
This work was supported by the Rural and Environment Science and Analytical Services Division of the Scottish Government (CoE – CXC).
ClimateXChange
Edinburgh Climate Change Institute
High School Yards
Edinburgh EH1 1LZ
+44 (0) 131 651 4783
If you require the report in an alternative format such as a Word document, please contact info@climatexchange.org.uk or 0131 651 4783.
Note “Standard efficiency measure” includes draughtproofing, reduced infiltration and hot water tank insulation. All packages except radiator upgrades in the Lower cost retrofit case include standard efficiency measures. ↑